13.3 Pfannenberg units with Standard- or Comfort-Controller

The following table describes the technical cause as well as the fault remedy as a function of the unit characteristics.

Air short-circuit:

 An air short-circuit develops, if cool air at the air outlet of the cooling unit is led by means of power components built directly in front of it in an

unfavourable way, not into the switch cabinet, but directly to the air inlet of the cooling unit. The consequence is overheating of the power components due to the
lack of cooling.

14 Warranty Conditions

Warranty becomes null and void:
• in case of improper usage of the unit, noncompliance with ope-

rating conditions or nonobservance of instructions;

• If operated in rooms in which corrosives or acids are present in

the atmosphere;

• in case of damage caused by contaminated or jammed air filters;
• if a non-authorised person interrupts the cooling circulation,

modifies the unit or changes the serial number;

• in case of damage caused by transport or by accidents;

• for the exchange of parts by non-authorized companies.
In order to maintain your warranty rights please observe the following
when returning the unit:
• Enclose an exact description of the fault in the shipping package.
• Enclose proof of delivery (delivery note or copy of invoice).
• Return the unit together with all accessories; use the original

packaging or packaging of equivalent quality, send the unit frei-
ght prepaid and covered by an adequate transport insurance.
Observe the hints on transport mentioned in section 2.

Unit characteristics

Compressor:

OFF

Internal fan:

OFF

External fan:

OFF

Status LED:

OFF

Fault signal contact:

open

Compressor:

ON

Internal fan:

ON

External fan:

ON

Status LED:

flashing (seq. 3)

ult signal contact:

open

Compressor:

OFF

Internal fan:

OFF

External fan:

OFF

Status LED:

flashing (seq. 1)

Fault signal contact:

closed

Compressor:

OFF

Internal fan:

ON

External fan:

ON

Status LED:

flashing (seq. 2)

Fault signal contact:

open

Compressor:

OFF

Internal fan:

OFF

External fan:

OFF

Status LED:

flashing (seq. 1)

Fault signal contact:

open

Compressor:

ON

Internal fan:

ON

External fan:

ON

Status LED:

flashing (seq. 1)

Fault signal contact:

open

Compressor:

ON

Internal fan:

ON

External fan:

ON

Status LED:

flashing (seq. 2)

Fault signal contact:

open

Compressor:

normal control
characteristics

Internal fan:

ON

External fan:

normal control
characteristics

Status LED:

flashing (seq. 1)

Fault signal contact:

open

Pos

1

2

3

4

5

6

7

8

Technical causes

There is no supply of voltage to the unit.

The test mode of the unit is active. This
mode is left automatically at the latest after
60 s.

The input for the door limit switch is open
e.g. as a result of a switch cabinet door not
closed or a bridge not set.

High pressure pressostat or motor
protection switch has responded
(overheating). Compressor switches on
again automatically after the fault has been
remedied (cooling) with a delay of   30 s.

Unit adjustment by means of the coding
switch on the control electronics is not
plausible. The unit setting must be changed.

The upper temperature limit of the switch
cabinet has been exceeded.

The temperature sensor TS1 is defective or
has not been detected.

In the switch cabinet, if a short circuit in the
air circuit* occurs, no effective cooling of the
switch cabinet is possible.
Air-conditioning is requested within short
cycle times.

Fault remedy

Check back-up fuse and/or connect supply
voltage

The unit switches to test mode once after
each new connection to the power supply.
No remedy of fault necessary.

Insert link, close door contact switch or,
with an engaged door contact switch,
close the door

Clean filter mat or heat exchanger in the
external circulation. Possibly check the
power dissipation in the switch cabinet to
the installed cooling capacity of the air
conditioner.

Observe the operating instructions and
note the coding key of the coding switch.

Clean filter mat or heat exchanger in the
external circulation. Possibly check the
power dissipation in the switch cabinet to
the installed cooling capacity of the air
conditioner.

Replace the contact sensor TS1 or replace
the complete electronic control with a
fixed-wired temperature sensor
Get in touch with the service department.

Relocate the power components in the
switch cabinet or relocate the cooling unit.
Select a top-mounting cooling unit or side-
mounting cooling unit as an alternative
depending on the space situation.

Summary of Contents for DTFI 9021

Page 1: ...etriebs und Montageanleitung f r Anbau und Einbau K hlger te DTI DTFI 9021 12 2007 085408076a Operating and assembly instructions for side mounted and built in cooling units DTI DTFI 9021 DTI DTFI 902...

Page 2: ...triebs und Montageanleitung f r Anbau und Einbau K hlger te Serie DTI DTFI 9021 17 Operating and assembly instructions for side mounted and built in cooling units series DTI DTFI 9021 10 DTI DTFI 9021...

Page 3: ...6 4 7 4 7 1 4 7 2 4 8 5 8 1 5 8 2 DTS 9x41 5 8 3 DTI 9x41 5 8 4 6 9 6 10 6 10 1 6 10 2 6 10 3 6 10 4 7 10 5 7 10 6 7 10 7 7 11 7 11 1 7 11 2 7 12 7 13 8 13 1 8 13 2 8 13 3 Pfannenberg Standard Comfort...

Page 4: ...4 085 408 076a 6 Pfannenberg IP 54 11 7 7 1 1 2 3 4 5 6 7 1 2 5 3 4 6 7 2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 1 2 7 8 6 4 3 14 13 12 11 9 10 5 3 3 1 3 2 4 Pfannenberg Pfannenberg PCB PCT 5...

Page 5: ...408 076a 5 8 8 1 200 8 2 DTS 9x41 1 1 DTI 2 2 1 2 3 M6 A M 6 D 2 4 C B Y Z 5 6 C B 7 0 5 2 5 2 AWG20 AWG14 8 8 4 8 3 DTI 9x41 1 2 C B Y Z 3 1 2 3 1 DTFI 2 3 4 4 A 2 5 6 C B 7 0 5 2 5 2 AWG20 AWG14 8...

Page 6: ...6 085 408 076a 9 10 3 45 C 10 10 1 10 2 10 4 13 10 3 30 30 8 4 3 400 440 400 440 20 20 230 1...

Page 7: ...085 408 076a 7 10 4 t 0 30 t 30 t 32 t 34 64 13 2 10 5 10 5 10 4 10 6 13 10 7 11 11 1 1 2 3 11 2 11 1 12 4...

Page 8: ...8 085 408 076a 13 13 1 13 2 1 5s 1s 1s 1s 2 1s 1s 3 1s 1s 1s 1s...

Page 9: ...085 408 076a 9 13 3 Pfannenberg 1 OFF OFF OFF OFF 2 ON ON ON 3 60 3 OFF OFF OFF 1 4 OFF ON ON 2 30 5 OFF OFF OFF 1 6 ON ON ON 1 7 ON ON ON 2 TS1 TS1 8 ON 1 2 14...

Page 10: ...trictly observed material damage may be caused Hint A hint contains additional information on the action or instruction described 2 Handling 2 1 Transport Lift cooling unit only by the casing or with...

Page 11: ...be carried out by authorized specialist personnel Compliance with applicable safety and environmental regulations is mandatory Hazard Isolate the cooling unit from the mains before carrying out any cl...

Page 12: ...Lay the tube with a downward fall Shorten as required If the tube has been extended by means of a connector and a further tube the additional weight of the tube must be appropriately supported so that...

Page 13: ...the value indicated Frequency must be within 3 Hz of the value indicated Ambient temperature must be below 45 C for options see Techn data sheet Use the unit such that the cooling capacity suits the...

Page 14: ...sheet for factory settings CAUTION Changes to the parameters of the unit set in the works may be made only by authorised persons Isolate the cooling unit from the mains before changing the DIP switsch...

Page 15: ...for usage exceeded Lack of coolant Heat exchanger contaminated Fan in internal airflow circuit faulty Fan in external airflow circuit faulty Air not circulationg properly inside the switch cabinet Cod...

Page 16: ...nal fan ON Status LED flashing seq 1 Fault signal contact open Compressor ON Internal fan ON External fan ON Status LED flashing seq 2 Fault signal contact open Compressor normal control characteristi...

Page 17: ...Leben und Gesundheit besteht Gefahr Bedeutet dass bei Nichtbeachtung der nachfolgend beschriebenen Ma nahmen Gefahr f r Leben und Gesundheit durch Stromschlag besteht Achtung Bedeutet dass bei Nichtb...

Page 18: ...l durchgef hrt werden Es sind die entsprechenden Sicherheits und Umweltschutzvorschriften zu beachten Gefahr Schalten Sie vor Reinigungs und Wartungsarbeiten das K hlger t spannungsfrei Es d rfen nur...

Page 19: ...iehe Beiblatt Schlauch mit Gef lle verlegen Bei Bedarf k rzen Wird der Schlauch durch ein Anschlussst ck weiteren Schlauch erweitert ist das zus tzliche Gewicht des Schlauchs entsprechend abzufangen s...

Page 20: ...n Wert liegen Die Umgebungstemperatur muss unterhalb 45 C Optionen siehe Beiblatt liegen Das Ger t muss so eingesetzt werden dass die angegebene K lteleistung den tats chlichen Bedarf decken kann Es d...

Page 21: ...g eingestellten Parametern des Ger tes d rfen nur von autorisierten Personen durchgef hrt werden Schalten Sie das Ger t vor nderung der Kodierschalter Ein stellung spannungsfrei da sonst die ver ndert...

Page 22: ...nicht ausreichend Ger t k hlt nur manchmal Kondensatbildung im Schaltschrank Kondensat l uft nicht ab m gliche Ursache Temperatureinstellung zu hoch eingestellt Einsatzgrenzen berschritten K ltemitte...

Page 23: ...triebsanzeige blinkend Folge 1 St rmeldekontakt ge ffnet Verdichter ON Innenl fter ON Au enl fter ON Betriebsanzeige blinkend Folge 2 St rmeldekontakt ge ffnet Verdichter normales Regelverh Innenl fte...

Page 24: ...g GmbH Werner Witt Stra e 1 D 21035 Hamburg Postfach 80 07 47 D 21035 Hamburg Telefon 040 7 34 12 0 Telefax 040 7 34 12 345 http www Pfannenberg com e mail technical support pfannenberg com 12 2007 08...

Reviews: