Danger!

Burr caused by production may be present on the metal
edges of the unit. Always wear protective gloves when car-
rying out maintenance work and installation.
In case of a warranty claim exact details on the fault (photo-
graph, if possible) and the indication of type and serial num-
ber of the cooling unit are required.

3

Scope of delivery and options

3.1

Scope of delivery

The Scope of delivery includes:
• cooling unit (with connection for door contact switch)
• Enclosed package (among other things sealing profile,

fastening material, electrical plug-type connectors)

• special accessories, if applicable.

3.2

Options

The following parts may be ordered separately:
– further options on request or in accordance with the catalogue.

4

General Information

• Old devices can be properly disposed of by Pfannenberg.  They

must be sent to one of our works shipment/postage paid.

• All cooling units produced by 

Pfannenberg 

are free from

siliconecompounds,

PCB,

PCT,

asbestos,

formaldehyde,

cadmium,

substances impairing wetting.

• Every cooling unit is checked to ensure that it is tight.
• Prior to delivery the electrical safety of every cooling unit is

factory tested.

5

ID Plate and Technical Data

For installation and maintenance, note the data on the ID plate; it is
to be found on the back of the cooling unit casing
The technical details applicable to the cooling unit are in the Techn.
data sheet.

6

Safety

Cooling units produced by 

Pfannenberg 

are designed for  dissipating

heat from switch cabinets (IP 54). During each cooling process
condensate can be produced. The cooling unit is only suitable for
stationary operation.
The cooling unit may only be used under the ambient conditions
specified on the Techn. data sheet.
The cooling unit is to a large measure maintenance-free (see Section
11).
Every other use is considered as non-authorized use making any
warranty null and void.
The electrical equipment must be regularly checked. Any faults such
as loose connections or scorched cables must be removed
immediately.
Work on the cooling system and on electrical components may only
be carried out by authorized specialist personnel.
 Compliance with applicable safety and environmental regulations
is mandatory.

Hazard!

Isolate the cooling unit from the mains before carrying out
any cleaning or maintenance operations.

Only original spare parts may be used.

7

Function

7.1

Principles of function

1

Compressor

2

Heat exchanger
(condenser)

3

Expansion valve

4

Heat exchanger
(evaporator)

5

fan, exterior circulation

6

fan, inner circulation

7

Electronic control system with temperature sensor

The compressor (1) compresses the refrigerant until high pressure
is achieved. During this process temperature increases. In the
condenser (2) heat is dissipated to ambient air, the coolant becoming
liquid. The condenser fan (5) of the condensator takes ambient air
in through the condenser, then it releases the air.
In the expansion valve (3) the pressure of the coolant drops. In the
evaporator (4) the coolant absorbs heat from the air in the switch
cabinet and evaporates. Thus, the air in the switch cabinet cools
down. At the same time the air inside the switch cabinet is being
dehumidified. The evaporator fan (6) sucks the air out of the switch
cabinet via the evaporator, the cooled air flows back to the switch
cabinet.
The cooling unit is electronically controlled. For that purpose a
temperature sensor records the temperature of the air inside the
switch cabinet (7).
The refrigerant is not detrimental to the ozonosphere; it is hardly
combustible.

7.2

Condensate

During cooling on the evaporator the moisture removed from the air
is collected as condensate. In order to avoid any damage to the
switch cabinet and the cooling unit, the condensate must be
discharged.
The condensate is discharged in the following way:
• In case of normal condensate drainage a reservoir collects the

condensate which is then drained by means of a hose.

Always ensure that the condensate is drained properly (safety-
drainage).
Excessive condensation can occur if, for example, the switch
cabinet is not sealed or if the internal temperature of the switch
cabinet is frequently below the dew point.

unit type

refrigerant

nominal voltage

pressure of
refrigerant

frequency

serial number

type of fusing

fusing

electrical
energy

exterior/interior
conditions

cooling
capacity

starting
current

nominal current

Summary of Contents for DTFI 9021

Page 1: ...etriebs und Montageanleitung f r Anbau und Einbau K hlger te DTI DTFI 9021 12 2007 085408076a Operating and assembly instructions for side mounted and built in cooling units DTI DTFI 9021 DTI DTFI 902...

Page 2: ...triebs und Montageanleitung f r Anbau und Einbau K hlger te Serie DTI DTFI 9021 17 Operating and assembly instructions for side mounted and built in cooling units series DTI DTFI 9021 10 DTI DTFI 9021...

Page 3: ...6 4 7 4 7 1 4 7 2 4 8 5 8 1 5 8 2 DTS 9x41 5 8 3 DTI 9x41 5 8 4 6 9 6 10 6 10 1 6 10 2 6 10 3 6 10 4 7 10 5 7 10 6 7 10 7 7 11 7 11 1 7 11 2 7 12 7 13 8 13 1 8 13 2 8 13 3 Pfannenberg Standard Comfort...

Page 4: ...4 085 408 076a 6 Pfannenberg IP 54 11 7 7 1 1 2 3 4 5 6 7 1 2 5 3 4 6 7 2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 1 2 7 8 6 4 3 14 13 12 11 9 10 5 3 3 1 3 2 4 Pfannenberg Pfannenberg PCB PCT 5...

Page 5: ...408 076a 5 8 8 1 200 8 2 DTS 9x41 1 1 DTI 2 2 1 2 3 M6 A M 6 D 2 4 C B Y Z 5 6 C B 7 0 5 2 5 2 AWG20 AWG14 8 8 4 8 3 DTI 9x41 1 2 C B Y Z 3 1 2 3 1 DTFI 2 3 4 4 A 2 5 6 C B 7 0 5 2 5 2 AWG20 AWG14 8...

Page 6: ...6 085 408 076a 9 10 3 45 C 10 10 1 10 2 10 4 13 10 3 30 30 8 4 3 400 440 400 440 20 20 230 1...

Page 7: ...085 408 076a 7 10 4 t 0 30 t 30 t 32 t 34 64 13 2 10 5 10 5 10 4 10 6 13 10 7 11 11 1 1 2 3 11 2 11 1 12 4...

Page 8: ...8 085 408 076a 13 13 1 13 2 1 5s 1s 1s 1s 2 1s 1s 3 1s 1s 1s 1s...

Page 9: ...085 408 076a 9 13 3 Pfannenberg 1 OFF OFF OFF OFF 2 ON ON ON 3 60 3 OFF OFF OFF 1 4 OFF ON ON 2 30 5 OFF OFF OFF 1 6 ON ON ON 1 7 ON ON ON 2 TS1 TS1 8 ON 1 2 14...

Page 10: ...trictly observed material damage may be caused Hint A hint contains additional information on the action or instruction described 2 Handling 2 1 Transport Lift cooling unit only by the casing or with...

Page 11: ...be carried out by authorized specialist personnel Compliance with applicable safety and environmental regulations is mandatory Hazard Isolate the cooling unit from the mains before carrying out any cl...

Page 12: ...Lay the tube with a downward fall Shorten as required If the tube has been extended by means of a connector and a further tube the additional weight of the tube must be appropriately supported so that...

Page 13: ...the value indicated Frequency must be within 3 Hz of the value indicated Ambient temperature must be below 45 C for options see Techn data sheet Use the unit such that the cooling capacity suits the...

Page 14: ...sheet for factory settings CAUTION Changes to the parameters of the unit set in the works may be made only by authorised persons Isolate the cooling unit from the mains before changing the DIP switsch...

Page 15: ...for usage exceeded Lack of coolant Heat exchanger contaminated Fan in internal airflow circuit faulty Fan in external airflow circuit faulty Air not circulationg properly inside the switch cabinet Cod...

Page 16: ...nal fan ON Status LED flashing seq 1 Fault signal contact open Compressor ON Internal fan ON External fan ON Status LED flashing seq 2 Fault signal contact open Compressor normal control characteristi...

Page 17: ...Leben und Gesundheit besteht Gefahr Bedeutet dass bei Nichtbeachtung der nachfolgend beschriebenen Ma nahmen Gefahr f r Leben und Gesundheit durch Stromschlag besteht Achtung Bedeutet dass bei Nichtb...

Page 18: ...l durchgef hrt werden Es sind die entsprechenden Sicherheits und Umweltschutzvorschriften zu beachten Gefahr Schalten Sie vor Reinigungs und Wartungsarbeiten das K hlger t spannungsfrei Es d rfen nur...

Page 19: ...iehe Beiblatt Schlauch mit Gef lle verlegen Bei Bedarf k rzen Wird der Schlauch durch ein Anschlussst ck weiteren Schlauch erweitert ist das zus tzliche Gewicht des Schlauchs entsprechend abzufangen s...

Page 20: ...n Wert liegen Die Umgebungstemperatur muss unterhalb 45 C Optionen siehe Beiblatt liegen Das Ger t muss so eingesetzt werden dass die angegebene K lteleistung den tats chlichen Bedarf decken kann Es d...

Page 21: ...g eingestellten Parametern des Ger tes d rfen nur von autorisierten Personen durchgef hrt werden Schalten Sie das Ger t vor nderung der Kodierschalter Ein stellung spannungsfrei da sonst die ver ndert...

Page 22: ...nicht ausreichend Ger t k hlt nur manchmal Kondensatbildung im Schaltschrank Kondensat l uft nicht ab m gliche Ursache Temperatureinstellung zu hoch eingestellt Einsatzgrenzen berschritten K ltemitte...

Page 23: ...triebsanzeige blinkend Folge 1 St rmeldekontakt ge ffnet Verdichter ON Innenl fter ON Au enl fter ON Betriebsanzeige blinkend Folge 2 St rmeldekontakt ge ffnet Verdichter normales Regelverh Innenl fte...

Page 24: ...g GmbH Werner Witt Stra e 1 D 21035 Hamburg Postfach 80 07 47 D 21035 Hamburg Telefon 040 7 34 12 0 Telefax 040 7 34 12 345 http www Pfannenberg com e mail technical support pfannenberg com 12 2007 08...

Reviews: