background image

085 408 076a

13

8.4

Power connection

CAUTION:

• The cooling unit must be connected to the mains by means of a

disconnecting device with a contact gap of at least 3 mm when
switched off.

• No temperature control must be series-connected to the cooling

unit feed.
The fuse as indicated on the ID plate must be series-connected
as line protection.

• Power connection and repairs, if applicable, may only be car-

ried out by authorized trained electricians.

Power supply connection (mains):

Both mains voltage and frequency must correspond to the nominal
values indicated on the ID plate of the cooling unit.
• The installation of the power cable is not subject to any special

requirements

Attention: The cooling unit may be damaged if the

voltage is too high.

Refers to cooling units for nominal voltages 400 V/440V.
As an option, some units, different to the standard (400 V/
440 V), may be connected to a different mains voltage (For
voltage range see Techn. data sheet). The feed cables on
the transformer primary must be unclamped for this.

Door contact:

The door contact is supplied form the cooling unit with an extra-low
voltage (<20V, 20 mA).
• In order to avoid any disruptive influences, it is recommended

that a sheathed cable with twisted pair leads be used. The screen
can be secured on one side to the PE connection point provi-
ded on the cooling unit.

• If the use of sheathed cables is not possible, during installation of

the cables it must be ensured that they are not routed in the imme-
diate vicinity of potential interference sources (e.g. supply lines, com-
ponents with relatively high electromagnetic emission).

WARNING: No external voltage may be applied.

If no door-contact switch is used, the connecting contacts
are to be bridged.

Centralised fault indication:

For connection of the fault signal line there are 2 connection contacts
and/or connecting lines available (see circuit diagram on the Techn.
data sheet)
The installation of the fault signal line is not subject to any special
requirements.

WARNING: The contact may be loaded with

max. 230 V, 1A.

9

Operating Conditions

• Voltage must be within ± 10 % of the value indicated.

Frequency must be within ± 3 Hz of the value indicated.

• Ambient temperature must be below 45 °C (for options see Techn.

data sheet).

• Use the unit such that the cooling capacity suits the actual de-

mand.

• Use refrigerant as indicated only.
• Use genuine spare parts only.

10 Putting into operation and function

10.1 General remarks

The cooling unit is provided with an electronic control system. The
drawn-in switch cabinet internal air temperature is measured by a
temperature sensor. By means of a DIP switch on the control board,
different switch cabinet temperatures as well as upper limit temperatures
can be selected (see Techn. data sheet).
Exceeding the limit temperature generates an alarm.

Warning!

Ambient conditions and temperature in the switch cabinet must
be in accordance with the values indicated in the Techn. data
sheet.

Warning! Too little heat transfer at the heat exchan-

ger in the external circuit (condenser).

The cooling unit may only be operated with cover, otherwi-
se heat dissipation at the condenser is not sufficient, and
the cooling unit may be damaged.
Immediately after the switch-on of the service voltage, the
unit goes into the start-up/test mode. After that the evapo-
rator fan continues to run. Compressor and condenser fans
run on as required (the temperature of the switching thres-
hold (T

set

) has been reached, or are switched off (tempera-

ture lower than switching threshold (T

set

)).

• Free discharge of any condensate produced must be provided

to ensure trouble-free operation.

10.2 Indicator elements

The cooling unit has an operational display in the form of a LED on the
external hood of the unit. If the light of this indicator remains on when
the supply voltage is applied it shows that the unit is in the normal
operating mode. If a fault occurs or if the unit is in the start-up or test
mode, this indicator lights up in various flashing sequences which make
it easier to diagnose fault in the unit (see Sections 10.4 and 13)

10.3 Test mode / start-up

The test mode is basically activated after renewed connection of
the supply voltage and is independent of the instantaneous ambient
conditions when the door contact is closed.
First of all the unit runs through a start-up mode lasting 30 seconds
which is followed by a test mode lasting 30 seconds.

Summary of Contents for DTFI 9021

Page 1: ...etriebs und Montageanleitung f r Anbau und Einbau K hlger te DTI DTFI 9021 12 2007 085408076a Operating and assembly instructions for side mounted and built in cooling units DTI DTFI 9021 DTI DTFI 902...

Page 2: ...triebs und Montageanleitung f r Anbau und Einbau K hlger te Serie DTI DTFI 9021 17 Operating and assembly instructions for side mounted and built in cooling units series DTI DTFI 9021 10 DTI DTFI 9021...

Page 3: ...6 4 7 4 7 1 4 7 2 4 8 5 8 1 5 8 2 DTS 9x41 5 8 3 DTI 9x41 5 8 4 6 9 6 10 6 10 1 6 10 2 6 10 3 6 10 4 7 10 5 7 10 6 7 10 7 7 11 7 11 1 7 11 2 7 12 7 13 8 13 1 8 13 2 8 13 3 Pfannenberg Standard Comfort...

Page 4: ...4 085 408 076a 6 Pfannenberg IP 54 11 7 7 1 1 2 3 4 5 6 7 1 2 5 3 4 6 7 2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 1 2 7 8 6 4 3 14 13 12 11 9 10 5 3 3 1 3 2 4 Pfannenberg Pfannenberg PCB PCT 5...

Page 5: ...408 076a 5 8 8 1 200 8 2 DTS 9x41 1 1 DTI 2 2 1 2 3 M6 A M 6 D 2 4 C B Y Z 5 6 C B 7 0 5 2 5 2 AWG20 AWG14 8 8 4 8 3 DTI 9x41 1 2 C B Y Z 3 1 2 3 1 DTFI 2 3 4 4 A 2 5 6 C B 7 0 5 2 5 2 AWG20 AWG14 8...

Page 6: ...6 085 408 076a 9 10 3 45 C 10 10 1 10 2 10 4 13 10 3 30 30 8 4 3 400 440 400 440 20 20 230 1...

Page 7: ...085 408 076a 7 10 4 t 0 30 t 30 t 32 t 34 64 13 2 10 5 10 5 10 4 10 6 13 10 7 11 11 1 1 2 3 11 2 11 1 12 4...

Page 8: ...8 085 408 076a 13 13 1 13 2 1 5s 1s 1s 1s 2 1s 1s 3 1s 1s 1s 1s...

Page 9: ...085 408 076a 9 13 3 Pfannenberg 1 OFF OFF OFF OFF 2 ON ON ON 3 60 3 OFF OFF OFF 1 4 OFF ON ON 2 30 5 OFF OFF OFF 1 6 ON ON ON 1 7 ON ON ON 2 TS1 TS1 8 ON 1 2 14...

Page 10: ...trictly observed material damage may be caused Hint A hint contains additional information on the action or instruction described 2 Handling 2 1 Transport Lift cooling unit only by the casing or with...

Page 11: ...be carried out by authorized specialist personnel Compliance with applicable safety and environmental regulations is mandatory Hazard Isolate the cooling unit from the mains before carrying out any cl...

Page 12: ...Lay the tube with a downward fall Shorten as required If the tube has been extended by means of a connector and a further tube the additional weight of the tube must be appropriately supported so that...

Page 13: ...the value indicated Frequency must be within 3 Hz of the value indicated Ambient temperature must be below 45 C for options see Techn data sheet Use the unit such that the cooling capacity suits the...

Page 14: ...sheet for factory settings CAUTION Changes to the parameters of the unit set in the works may be made only by authorised persons Isolate the cooling unit from the mains before changing the DIP switsch...

Page 15: ...for usage exceeded Lack of coolant Heat exchanger contaminated Fan in internal airflow circuit faulty Fan in external airflow circuit faulty Air not circulationg properly inside the switch cabinet Cod...

Page 16: ...nal fan ON Status LED flashing seq 1 Fault signal contact open Compressor ON Internal fan ON External fan ON Status LED flashing seq 2 Fault signal contact open Compressor normal control characteristi...

Page 17: ...Leben und Gesundheit besteht Gefahr Bedeutet dass bei Nichtbeachtung der nachfolgend beschriebenen Ma nahmen Gefahr f r Leben und Gesundheit durch Stromschlag besteht Achtung Bedeutet dass bei Nichtb...

Page 18: ...l durchgef hrt werden Es sind die entsprechenden Sicherheits und Umweltschutzvorschriften zu beachten Gefahr Schalten Sie vor Reinigungs und Wartungsarbeiten das K hlger t spannungsfrei Es d rfen nur...

Page 19: ...iehe Beiblatt Schlauch mit Gef lle verlegen Bei Bedarf k rzen Wird der Schlauch durch ein Anschlussst ck weiteren Schlauch erweitert ist das zus tzliche Gewicht des Schlauchs entsprechend abzufangen s...

Page 20: ...n Wert liegen Die Umgebungstemperatur muss unterhalb 45 C Optionen siehe Beiblatt liegen Das Ger t muss so eingesetzt werden dass die angegebene K lteleistung den tats chlichen Bedarf decken kann Es d...

Page 21: ...g eingestellten Parametern des Ger tes d rfen nur von autorisierten Personen durchgef hrt werden Schalten Sie das Ger t vor nderung der Kodierschalter Ein stellung spannungsfrei da sonst die ver ndert...

Page 22: ...nicht ausreichend Ger t k hlt nur manchmal Kondensatbildung im Schaltschrank Kondensat l uft nicht ab m gliche Ursache Temperatureinstellung zu hoch eingestellt Einsatzgrenzen berschritten K ltemitte...

Page 23: ...triebsanzeige blinkend Folge 1 St rmeldekontakt ge ffnet Verdichter ON Innenl fter ON Au enl fter ON Betriebsanzeige blinkend Folge 2 St rmeldekontakt ge ffnet Verdichter normales Regelverh Innenl fte...

Page 24: ...g GmbH Werner Witt Stra e 1 D 21035 Hamburg Postfach 80 07 47 D 21035 Hamburg Telefon 040 7 34 12 0 Telefax 040 7 34 12 345 http www Pfannenberg com e mail technical support pfannenberg com 12 2007 08...

Reviews: