13.1 General errors

-  No  message via the service indicator

13.2 Fault diagnosis

- Message via the service indicator

If a fault occurs in the cooling unit, the status indicator goes over to flashing mode which in conjunction with the unit characteristics is to
make initial fault diagnosis easier.
Flashing sequences in the fault mode can be:

Status indicator, flashing sequence 1:

(5s, 1s, 1s, 1s)  with periodic repetition

(User error)

Status indicator, flashing sequence 2:

(1s, 1s)  with periodic repetition

(Unit fault)

Status indicator, flashing sequence 3:

(1s, 1s, 1s, 1s)  with periodic repetition

(Test/start-up mode)

Fault

Unit fails to cool, fan in an
internal airflow circuit is running

Unit fails to cool cufficiently.

Unit only cools irregularly

Condensate accumulates in
switch cabinet

Condensate fails to drain

Possible cause(s)

Temperature setting too high

Thresholdvalues for usage exceeded.

Lack of coolant

Heat exchanger contaminated.

Fan in internal airflow circuit faulty. Fan in
external airflow circuit faulty.

Air not circulationg properly inside the switch
cabinet

Coding switch incorrectly set or defective.

Blow-out temperature too low

Switch cabinet not sufficiently sealedt.

Condensate drainage clogged.

Remedy

Check temperature setting.

Check ambient temperature and internal load.

Call authorized specialist, check unit for leaks

Clean heat exchanger.

Call authorized specialist, replace fan.

Check assemblies and air circulation inside
switch cabinet. Air intake and eexhaust into/
from cooling unit into switch cabinet must be
inimpeded.

Check coding switch and cable connections.

Set higher temperature at thermostat..

Close switch cabinet door.
Remedy leakage at switch cabinet.

Clean condensate drainage. Condensate
drainage hose must be inclined downward
without showing a bend.

13 What to do if ...

... in spite of your care and attention a fault occurs?
Check the following points first. If the fault is not then cleared, call an authorized specialist.

Summary of Contents for DTFI 9021

Page 1: ...etriebs und Montageanleitung f r Anbau und Einbau K hlger te DTI DTFI 9021 12 2007 085408076a Operating and assembly instructions for side mounted and built in cooling units DTI DTFI 9021 DTI DTFI 902...

Page 2: ...triebs und Montageanleitung f r Anbau und Einbau K hlger te Serie DTI DTFI 9021 17 Operating and assembly instructions for side mounted and built in cooling units series DTI DTFI 9021 10 DTI DTFI 9021...

Page 3: ...6 4 7 4 7 1 4 7 2 4 8 5 8 1 5 8 2 DTS 9x41 5 8 3 DTI 9x41 5 8 4 6 9 6 10 6 10 1 6 10 2 6 10 3 6 10 4 7 10 5 7 10 6 7 10 7 7 11 7 11 1 7 11 2 7 12 7 13 8 13 1 8 13 2 8 13 3 Pfannenberg Standard Comfort...

Page 4: ...4 085 408 076a 6 Pfannenberg IP 54 11 7 7 1 1 2 3 4 5 6 7 1 2 5 3 4 6 7 2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 1 2 7 8 6 4 3 14 13 12 11 9 10 5 3 3 1 3 2 4 Pfannenberg Pfannenberg PCB PCT 5...

Page 5: ...408 076a 5 8 8 1 200 8 2 DTS 9x41 1 1 DTI 2 2 1 2 3 M6 A M 6 D 2 4 C B Y Z 5 6 C B 7 0 5 2 5 2 AWG20 AWG14 8 8 4 8 3 DTI 9x41 1 2 C B Y Z 3 1 2 3 1 DTFI 2 3 4 4 A 2 5 6 C B 7 0 5 2 5 2 AWG20 AWG14 8...

Page 6: ...6 085 408 076a 9 10 3 45 C 10 10 1 10 2 10 4 13 10 3 30 30 8 4 3 400 440 400 440 20 20 230 1...

Page 7: ...085 408 076a 7 10 4 t 0 30 t 30 t 32 t 34 64 13 2 10 5 10 5 10 4 10 6 13 10 7 11 11 1 1 2 3 11 2 11 1 12 4...

Page 8: ...8 085 408 076a 13 13 1 13 2 1 5s 1s 1s 1s 2 1s 1s 3 1s 1s 1s 1s...

Page 9: ...085 408 076a 9 13 3 Pfannenberg 1 OFF OFF OFF OFF 2 ON ON ON 3 60 3 OFF OFF OFF 1 4 OFF ON ON 2 30 5 OFF OFF OFF 1 6 ON ON ON 1 7 ON ON ON 2 TS1 TS1 8 ON 1 2 14...

Page 10: ...trictly observed material damage may be caused Hint A hint contains additional information on the action or instruction described 2 Handling 2 1 Transport Lift cooling unit only by the casing or with...

Page 11: ...be carried out by authorized specialist personnel Compliance with applicable safety and environmental regulations is mandatory Hazard Isolate the cooling unit from the mains before carrying out any cl...

Page 12: ...Lay the tube with a downward fall Shorten as required If the tube has been extended by means of a connector and a further tube the additional weight of the tube must be appropriately supported so that...

Page 13: ...the value indicated Frequency must be within 3 Hz of the value indicated Ambient temperature must be below 45 C for options see Techn data sheet Use the unit such that the cooling capacity suits the...

Page 14: ...sheet for factory settings CAUTION Changes to the parameters of the unit set in the works may be made only by authorised persons Isolate the cooling unit from the mains before changing the DIP switsch...

Page 15: ...for usage exceeded Lack of coolant Heat exchanger contaminated Fan in internal airflow circuit faulty Fan in external airflow circuit faulty Air not circulationg properly inside the switch cabinet Cod...

Page 16: ...nal fan ON Status LED flashing seq 1 Fault signal contact open Compressor ON Internal fan ON External fan ON Status LED flashing seq 2 Fault signal contact open Compressor normal control characteristi...

Page 17: ...Leben und Gesundheit besteht Gefahr Bedeutet dass bei Nichtbeachtung der nachfolgend beschriebenen Ma nahmen Gefahr f r Leben und Gesundheit durch Stromschlag besteht Achtung Bedeutet dass bei Nichtb...

Page 18: ...l durchgef hrt werden Es sind die entsprechenden Sicherheits und Umweltschutzvorschriften zu beachten Gefahr Schalten Sie vor Reinigungs und Wartungsarbeiten das K hlger t spannungsfrei Es d rfen nur...

Page 19: ...iehe Beiblatt Schlauch mit Gef lle verlegen Bei Bedarf k rzen Wird der Schlauch durch ein Anschlussst ck weiteren Schlauch erweitert ist das zus tzliche Gewicht des Schlauchs entsprechend abzufangen s...

Page 20: ...n Wert liegen Die Umgebungstemperatur muss unterhalb 45 C Optionen siehe Beiblatt liegen Das Ger t muss so eingesetzt werden dass die angegebene K lteleistung den tats chlichen Bedarf decken kann Es d...

Page 21: ...g eingestellten Parametern des Ger tes d rfen nur von autorisierten Personen durchgef hrt werden Schalten Sie das Ger t vor nderung der Kodierschalter Ein stellung spannungsfrei da sonst die ver ndert...

Page 22: ...nicht ausreichend Ger t k hlt nur manchmal Kondensatbildung im Schaltschrank Kondensat l uft nicht ab m gliche Ursache Temperatureinstellung zu hoch eingestellt Einsatzgrenzen berschritten K ltemitte...

Page 23: ...triebsanzeige blinkend Folge 1 St rmeldekontakt ge ffnet Verdichter ON Innenl fter ON Au enl fter ON Betriebsanzeige blinkend Folge 2 St rmeldekontakt ge ffnet Verdichter normales Regelverh Innenl fte...

Page 24: ...g GmbH Werner Witt Stra e 1 D 21035 Hamburg Postfach 80 07 47 D 21035 Hamburg Telefon 040 7 34 12 0 Telefax 040 7 34 12 345 http www Pfannenberg com e mail technical support pfannenberg com 12 2007 08...

Reviews: