STRATEGY
S, W
The strategy field can be used to identify comprising blocks.
This data is not controlled or used by the block.
ALERT_KEY
S, W
Identification number of the plant component. This information
can be used by the control computer, e.g., to sort alarms. Valid
values are 1 ... 65536.
MODE_BLK
S, W
Displays the current, permitted standard mode and the target
mode of the block. The target mode can be set to the values
"Auto" or "Out of Service".
Default: Auto
BLOCK_ERR
•
Out of service: When actual block mode is OOS
•
Block configuration error:
- Turn_On value of an on/off controller is lower than
Turn_Off value
- Maintenance Required or Out of Specification limits of
temperature, humidity, or frequency inputs not consistent
- On/off controller has input temperature difference and dif
-
ferent units are selected for temperature input 1 and 2
•
Other: If XD_ERROR is not zero
•
Sensor failure detected: If any bit in BINARY_ERRORS or
ANALOG_ERRORS is set
UPDATE_EVT
This parameter is used to signal to the PCS that a parameter
marked with "S" was overwritten provided that the PCS sup
-
ports alarm messages.
BLOCK_ALM
This parameter is used to signal to the PCS diagnostic mes
-
sages displayed in BLOCK_ERR, provided that the PCS sup
-
ports alarm messages.
XD_ERROR
Summary Field diagnostics status of the block:
•
Out of specification
•
Maintenance required
BINARY_ER
-
RORS
Leadbreakage or short circuit detection diagnostic information
of binary inputs.
ANALOG_ER
-
RORS
Failure information of analog inputs
•
Temperature input 1 and 2
•
Board temperature input
•
Board humidity input
•
Frequency input 1 and 2
FD_MR_AC
-
TIVE
Field diagnostics Maintenance Required error active for either
of the following:
•
Binary input 1 ... 8
•
Temperature input 1 and 2
•
Board temperature input
•
Board humidity input
•
Frequency input 1 and 2
FD_OOS_AC
-
TIVE
See FD_MR_ACTIVE, but for Out-of-Specification status
BINARY_IN
-
PUT_X (1-
8)
Binary input X value and status
TEMP_IN
-
PUT_X (1-
2)
Temperature input X value and status
TEMP_IN
-
PUT_INT
Board temperature value and status
Parameter
Char.
Description