Product Description
2
02
0-
11
37
Output I
relay , NO contact
Output type
selectable: diagnostic bus CH 1 , relay , NO
contact
Contact loading
250 V AC/ 6 A resistive load
Mechanical life
1 x 10
5
switching cycles
Response time
turn-on time 7 ms , turn-off time 3 ms
Switching frequency
6 min
-1
full load, 1200 min
-1
without load
Output II
Output type
selectable: diagnostic bus CH 2 , relay , NO
contact
Contact loading
250 V AC/ 6 A resistive load
Mechanical life
1 x 10
5
switching cycles
Response time
turn-on time 7 ms , turn-off time 3 ms
Switching frequency
6 min
-1
full load, 1200 min
-1
without load
Output III
Output type
selectable: common alarm , volt-free contact ,
NC contact
Connection
only for the connection to protected circuits
Voltage
50 V DC
Current
max. 1 A
Output IV
Output type
common alarm , buzzer
Electrical isolation
All circuits/FE
functional insulation acc. to IEC 62103, rated
insulation voltage 50 V
eff
Output I, II/other circuits
functional insulation acc. to IEC 62103, rated
insulation voltage 250 V
eff
Ethernet/Supply
functional insulation acc. to IEC 62103, rated
insulation voltage 50 V
eff
Ethernet/other circuits
functional insulation acc. to IEC 62103, rated
insulation voltage 50 V
eff
Fieldbus/other circuits
functional insulation acc. to IEC 62103, rated
insulation voltage 50 V
eff
Diagnostic Bus/other circuits
functional insulation acc. to IEC 62103, rated
insulation voltage 50 V
eff
Directive conformity
Electromagnetic compatibility
Directive 2004/108/EC
EN 61326-1:2013
Low voltage
Directive 73/23/EEC
EN 61010
Standard conformity
Electrical isolation
IEC 62103
Electromagnetic compatibility
NE 21
Degree of protection
IEC 60529
Fieldbus standard
IEC 61158-2