Appendix
2
02
0-
11
161
OUTPUT_
-
SOURCE
Record, W, S,
OOS
RELAY_OUTPUT_1
•
Not connected: The value of the output is the same as
defined if the IO_TB is in OOS mode
•
FF channel: The output value is provided through an FF
channel
•
BINARY_INPUT_1-8: Binary input 1 ... 8
•
ON_OFF_CONT_1-4: On/off controller 1 ... 4
•
Field diagnostics Fail: The output is set to 1 if a field diag
-
nostics Fail alarm is active
•
Field diagnostics Fail Inverted: Same as FD Fail but output
value is inverted
•
Field diagnostics Out of Spec: The output is set to 1 if a
field diagnostics Fail or Out of Specification alarm is active
•
Field diagnostics Out of Spec Inverted: Same as FD Out of
Specification but output value is inverted
•
Field diagnostics MR: : The output is set to 1 if a Field diag
-
nostics Fail, Out of Specification, or Maintenance Required
alarm is active
•
Field diagnostics MR Inverted: Same as FD MR, but output
value is inverted
•
Field diagnostics Check: The output is set to 1 if a field
diagnostics Fail, Out of Specification, Maintenance
Required, or Check function alarm is active
•
Field diagnostics Check Inverted: Same as FD Check, but
output value is inverted
RELAY_OUTPUT_2
See RELAY_OUTPUT_1
BUZZER_OUTPUT
See RELAY_OUTPUT_1
COMMON_ALARM_OUTPUT
See RELAY_OUTPUT_1
ON_OFF_
-
SET
-
TINGS_1/
ON_OFF_
-
SET
-
TINGS_2/
ON_OFF_
-
SET
-
TINGS_3/
ON_OFF_
-
SETTINGS_4
Record, W, S,
OOS
INPUT
Selects the input value for the on/off controller
•
Temperature input 1
•
Temperature input 2
•
Temperature difference (Temperature input 2
–
tempera
-
ture input 1)
•
Motherboard temperature
•
Motherboard humidity
•
Frequency input 1
•
Frequency input 2
ON_LEVEL
If input value > ON_LEVEL, then output value = 1
OFF_LEVEL
If input value < OFF_LEVEL, then output value = 0
OPTIONS
Invert: Inverts controller output.
SERI
-
AL_USAGE
For internal usage
Parameter
Char.
Description