DGW-FF Troubleshooting
LEDs
312
Segment / spur voltage is
too high
Fieldbus power supply
failed
Check and replace fieldbus
power supply
Device coupler failed
Check device couplers and
device coupler terminals
313
Segment / spur voltage is
too high compared to com
-
missioning
Fieldbus power supply
replaced with incompatible
model
Install correct fieldbus
power supply
Fieldbus power supply
failed
Check and replace fieldbus
power supply
This is possibly a result of
other errors
Solve other reported errors
first and check segment
again
Device coupler failed
Check device couplers and
device coupler terminals
314
Segment / spur voltage is
too high
Device coupler failed
Check device couplers and
device coupler terminals
Fieldbus power supply
failed
Check and replace fieldbus
power supply
315
FDH-1 appears to be con
-
nected to a spur
The signal level of one
device is too high
If FDH-1 is not connected
to a spur, re-check with a
specific segment record
316
Jitter is "Out of specifica
-
tion" and the signal level of
devices is too high for the
given topology
Not enough terminators
Check if a terminator is
installed on both ends of
the trunk
317
Jitter is Good and the sig
-
nal level of devices is too
high for the given topology
Not enough terminators
Check if a terminator is
installed on both ends of
the trunk
318
Jitter is "Good" and the sig
-
nal level of devices is too
high for the given topology
Not enough terminators
Check if a terminator is
installed on both ends of
the trunk
319
Jitter is "Out of specifica
-
tion" and devices signal
level is too high for the
given topology
Not enough terminators
Check if a terminator is
installed on both ends of
the trunk
320
Segment voltage too high
for the given topology
Wrong fieldbus power sup
-
ply installed or wrong topol
-
ogy configured
Replace fieldbus power
supply or correct topology
settings
ID
Phenomenon
Cause(s)
Action(s)
Behavior
Cause
Action
Green PWR is OFF
No power supply
Check power supply and wiring
Red ERR is ON
Hardware failure detected
Send device to manufacturer
Red ERR flashes
ADM address conflict
Check for ADMs that have the
same addresses, one connected
to CH1 other to CH2
Yellow Link/Act
flashes
Ethernet communication is active No error
Yellow CH1 is OFF
(FF Mode)
No ADMs detected on channel
Check wiring. Are there ADMs
supposed to be connected to the
channel?