2
02
0-
11
200
Appendix
Value Definitions and Priorities
8.12.2
OPC-AE Message Data
OPC-AE Message Names and Meaning
Overview of the Message Content
State Value
Meaning
0
No Error
1
Maintenance Required
2
Out of Specification
3
Hardware Error
4
Communication Error
State Data Quality
Meaning
BAD, Comm_FAILURE
A communication error between the OPC
server and the FDS server has occurred.
BAD, NON_SPECIFIC
FDS server has not polled the diagnostic
module yet (temporary state).
BAD, OUT_OF_SERVICE
A segment is disabled.
UNCERTAIN, NON_SPECIFIC
Occurs if the diagnostic module is connected
via the FDS to a Fuchs fieldbus gate
-
way that also processes alarms. This is an
invalid operating state.
GOOD
None of the above applies.
SummarizedState Priority
Meaning
HIGH
BAD, Comm_FAILURE
BAD, NON_SPECIFIC
UNCERTAIN, NON_SPECIFIC
LOW
GOOD
IGNORED
BAD, OUT_OF_SERVICE
Name
Meaning
Source of the message
Chain of tags separated by dots:
FDS.PORT.HD2-DM-A.SEGMENT
Type
CONDITION_BASED_EVENT
EventCategory
Fuchs ADM diagnostic condition
Severity
Weight of the alarm occurred
Message
Short description of the message occurred
Alarm Status
Message ID
Severity
Message Value
GOOD
0
101
Status returned to nor
-
mal
Maintenance required 1005
701
Bulk power supply
exceeds limits set
during commissioning
1004
701
Physical layer
exceeds limits set
during commissioning