ADDITIONAL FEATURES
Press the screen navigation arrow at the top right of the Master
Settings screen (Figure 13) to navigate to the secondary Master
Settings screen.
Figure 20 Secondary Master Settings Screen
• water saver regen:
Contains settings for setting
regenerations to save water by reducing backwash and
rinse time on a particular interval
• remote regen:
Contains settings for triggering a
regeneration via a remote input
• cl generation/low salt:
(international version only)
Contains settings to trigger chlorine generator for the
control
Water Saver Regeneration
From the secondary Master Settings screen (Figure 22) press
the
water saver regen.
button to display the Water Saver
Regen screen (Figure 23).
Figure 21 Water Saver Regen Screen
• water saver regen:
reduces backwash and rapid rinse
times on a particular interval. The reduced backwash
time is 50% less than the backwash time (rounded down
to the nearest minute, e.g. if the backwash time is set to
10 minutes, enabling the water saver regen function will
reduce the backwash time to 5 minutes).The reduced
rapid rinse time is 66% less than the rapid rinse time
(rounded down to the nearest minute, e.g. if the rapid
rinse time is set to 10 minutes, enabling the water
saver regen function will reduce the backwash time to 3
minutes).
• range:
1-25 regenerations (for example, a setting of 3
will produce 1 normal regeneration then 3 reduced water
saving regenerations).
From the secondary Master Settings screen (Figure 22) press
the
remote regen
button to display the Remote Regen screen.
Figure 22 Remote Regeneration Screen
• remote regeneration duration:
Contains settings for
triggering a regeneration via a remote input. Select a
value in seconds that the remote switch must be closed in
order to trigger the regeneration.
Connect a remote switch (such as a differential pressure
switch) to the remote start input terminals on the back of the
XTRI control board. When the remote switch remains closed for
the number of seconds specified in the Remote Regen screen,
a regeneration will be triggered regardless of volume, capacity,
or time remaining until the next scheduled regeneration.
Chlorine Generation/Low Salt
(international version only)
From the secondary Master Settings screen (Figure 22) press
the
cl generation/low salt
button to display the Chlorine Gen/
Low Salt screen (Figure 25).
Figure 23 Chlorine Gen/Low Salt Screen
• cl generation/low salt:
Contains settings to trigger
chlorine generator for the control (on/off)
• regen interval range:
1 to 255 regenerations
FLECK
5800/5810/5812 XTRI Service Manual • 13
Summary of Contents for FLECK 5800
Page 1: ...FLECK 5800 5810 5812 XTRI CONNECTED XTR2 SERVICE MANUAL pentair com...
Page 36: ...WATER CONDITIONER FLOW DIAGRAMS 5810 Upflow 36 FLECK 5800 5810 5812 XTRI Service Manual...
Page 37: ...WATER CONDITIONER FLOW DIAGRAMS 5810 Downflow FLECK 5800 5810 5812 XTRI Service Manual 37...