32
CALIBRATION COMMANDS
NOTE
:
Spaces must separate the command and settings. And each command string must
be terminated with a carriage return. (Use IBA 1<ENT> or IBA 2<ENT> to select base 1 or
2 before the CLP, CLW command.)
CLP - CaLibration Primary
COMMAND:
CLP 10.0 0.002 5.0 1 <ENT>
Enters the Calibration Factors
for the Primary weighing mode.
The example shown selects:
10.0 = Full scale Capacity
0.002 = Resolution
5.0 = Zero Range
1 = Units code (LBS)
CLU - CaLibration Print when Stable or Unstable
COMMAND
: CLU 0 <ENT>
Selects print when stable or
unstable Options: 0 = Selects
print when NOT stable 1 =
Selects print when Stable
(Required for NTEP)
CLW - CaLibration Weight
COMMAND:
CLW 3 <ENT>
Enters the Standard Two (2) Point
Weight Calibration using a filter
response time of 3
COMMAND:
CLW 3 5.0 <EN>
Enters the Weight Calibration
with a filter response of 3, and a
single point Calibration using a 5 lb.
weight.
COMMAND:
CLW 3 1 10 <ENT>
Enters the Weight Calibration
a filter response of 3, and using a 1
lb. and a 10 lb Weight.
NOTE:
Unless Calibration points are entered as part of the CLW command, Calibration
points will default to one half, and one, times the full scale primary weighing range.
RESPONSE TO TERMINAL
(parenthesis indicate local display message):
"Internal A/D Calibration.- Please Wait (------)
Place the following weights on the platform, press ENTER (either on terminal or scale) after
each:
0.000 lb*
(LoAd 0.000)
5.000 lb*
(LoAd 5.000) (* = Current weighing unit
10.000 lb*
(LoAd 10.000) selected will be displayed.)
0.000 lb*
(LoAd 0.000)
CLM - CaLibrate Modes
COMMAND:
CLM 0 0 1 <ENT> Turns off Canadian Legal for tradeconfiguration.
(0 = no, 1 = yes) turns off auto zero (0 = no,