WD-Z2 Series Installation Guidelines Rev.5
- 25 -
(1-2) Wiring the Signal Tower to equipment
CAUTION
Enforced
◆
Constant WDT power supply
- To operate the WDT, the power needs to be constantly supplied to the LR series Signal
Tower power line.
◆
Signal Tower Rated Voltage: 12 / 24 VDC
- Applicable Models: LR5-
□
01 / LR5-
□
02 /
LR6-
□
02
◆
Signal Tower Rated Voltage: 100 to 240 VAC
- Applicable Models: LR6-
□
M2
(1-3) Verify Operation
- The product's status
indicator lamp
can be used to determine the wireless communication status.
- After installation is complete, turn on the main power supply for the equipment and with
all of the signal tower
lamps off
, check the transmitter
indicator lamp
, verifying that
it is not in off state
. If the
indicator lamp
does
not turn on, the power supply wiring to the transmitter is not correct.
- The
indicator lamp
operates as follows:
Indicator Light
Wireless Connection Status
Green pulse
This status indicates a good status, in which the product can communicate directly with the
WDR without relying on other WDT units. (If the WDT and WDR are close together, within
tenths of centimeters, the WDT may display a red pulse.)
Amber pulse
Direct wireless connection with the WDR is not good, but the connection with nearby WDT
units are good. If a nearby WDT has a green pulse, the WDT will be used as a repeater for
communication.
Red pulse
Connection is not good with any WDR or WDT in the WD Network.
Red light
The product is waiting to join a WD Network.