P
AGE
39
ON
OFF
Actual Display
On/Off Display -
Use arrow keys
to turn on or off
Scroll Key
Numeric Display -
Use arrow keys
to change value
Up Arrow Key
Down Arrow
Key
Display Code
Description
Value
Pn
Profile Number
Actual Profile Number
tr
Time remaining in current Ramp or Soak
Actual time remaining value
(in whatever units were config
ured in the program mode for
Ptb)
E1, E2, E3
Event 1-3 status (if applicable)
on or oFF
SP
Current Setpoint
Actual Setpoint Value
ProC
Current Process Value
Actual Process Value
PLCt
Profile Loop Count remaining
Profile Loop count Value
Each code or value will only be displayed if they are appropriate. Each code or value will be
displayed for one second. This sequence will continue until any key is depressed.
To start a profile running at some point within the profile other than start can be accomplished
by using the Profile Continue mode. Press and release the SCROLL key until display is
PCon, then press the DOWN key. The display will be Pn; adjust the profile parameter values
as needed in the Profile Continue Configuration mode, then press the RUN key. The
instrument will execute the profile selected as directed by the information entered in the
Profile Continue mode. See Table 4-1, page 40. If you are running a profile and it is desired
to alter the profile you must go to hold and then scroll to the Off or Control mode before
entering Pcon.
Note: Pcon is not available when Profile Time Base (Ptb) in Program mode has been
set for Units Ramp Rate (EO Option).
PROFILE CONTINUE MODE FLOW CHART
Sn
rtr
Str
E1-E3
PLCt
Pn
PCon