P
AGE
30
DISPLAY
AVAILABLE
FACTORY YOUR
STEP
DESCRIPTION
CODE
SETTINGS
SETTING SETTING
19
Profile Time Base
Ptb
1=HHH.T - Hours & Tenths
3
2=HH.MM - Hours & Min.
3=MM.SS - Minutes & Sec.
EO Option
4=Units/Hr ramp rate;
Hrs. & Tenths soak time
5=Units/Hr ramp rate;
Hrs/Mins soak time
6=Units/Hr ramp rate;
Mins & Secs soak time
20
Profile Interrupt Action
PiA
0=Go to Off mode
1
1=Continue profile
2=Go into hold condition
3=Restart at the beginning
of the profile
21
Remote Run/Hold
rrH
0=Not selected
0
1=Selected. Remote
Run/Hold will override
controller front panel
when placed in hold
from remote source
2=Selected. Remote
Run/Hold will not
override controller
front panel when placed
in hold from remote source
22
Process Filter Factor
PFF
1 to 20 (# of scans aver.)
1
1=No filtering
23
Display Filter Factor
dFF
1 to 20 (# of scans aver.)
1
1=No filtering
Parameters 24 - 28 are for Extended Option (EO) Only
24
Current Output 1 Range
Co1r
0=0 to 20 mA
1
1=4 to 20 mA
25
Current Output 2 Range
Co2r
0=0 to 20 mA
1
1=4 to 20mA
26
Process Output
Pout
0=Not selected
0
1=Process Assigned to
Current Output 1
2=Process Assigned to
Current Output 2
3=Setpoint Assigned to
Current Output 1
4=Setpoint Assigned to
Current Output 2
27
Process/Setpoint
Pou
-9999 to 9999
2000
Output Upper Value
28
Process/Setpoint
PoL
-9999 to 9999
0
Output Lower Value