Input Selection
inPS
0=J T/C degrees C
1
1=J T/C degrees F
2=K T/C degrees C
3=K T/C degrees F
4=T T/C degrees C
5=T T/C degrees F
6=R T/C degrees C
7=R T/C degrees F
8=S T/C degrees C
9=S T/C degrees F
10=E T/C degrees C
11=E T/C degrees F
12=B T/C degrees C
13=B T/C degrees F
14=N T/C degrees C
15=N T/C degrees F
16=C T/C degrees C
17=C T/C degrees F
20=RTD degrees C
21=RTD degrees F
30=0 to 5VDC/0 to 20mA
31=1 to 5VDC/4 to 20mA
32=0 to 50mVDC
33=10 to 50mVDC
34=0 to 25mVDC
2
Input Correction
iCor
-300 to 300 degrees
0
3
Output 1
out1
1=On-Off - Direct
2
(cooling)
2=On-Off - Reverse
(heating)
3=Time Proportioning -
Direct (cooling)
4=Time Proportioning -
Reverse (heating)
5=Current Proportioning -
Direct (cooling)
6=Current Proportioning -
Reverse (heating)
7=Position Proportioning -
Open
4
Output 1Percent Limit
o1PL
0 to 100%
100
5
Output 2
out2
0=None
0
(Position Prop.
Direct - Close)
1=On-Off Direct (cooling)
2=On-Off - Reverse
(heating)
3=Time Proportioning -
Direct (cooling)
4=Time Proportioning -
Reverse (heating)
5=Current Proportioning -
Direct (cooling)
6=Current Proportioning -
Reverse (heating)
7=Position Proportioning
Reverse - Close
DISPLAY
AVAILABLE
FACTORY YOUR
STEP
DESCRIPTION
CODE
SETTINGS
SETTING SETTING
NOTE:
Fault detection
is not functional for 0-5 V
or 0-20mA inputs.