FIGURE 2-5
AC Power
Connect 115 VAC hot and neutral to terminals B and A respectively as illustrated below.
Connect 230 VAC as described below. Connect Earth ground to the ground screw as shown.
FIGURE 2-6
Thermocouple Input
Make thermocouple connections as illustrated below. Connect the positive lead of the
thermocouple to terminal 3, and the negative to terminal 1. For industrial environments with
comparatively high electrical noise levels, shielded thermocouples and extension wire are
recommended. Be sure that the input conditioning jumpers are properly positioned for a
thermocouple input. See Appendix A-2 (page 64) and A-3 (page 65 or 66).
115 VAC INSTRUMENT VOLTAGE
L1
L2
B
A
GROUND
.5 AMP*
FUSE
Rear View
*Supplied by customer
230 VAC INSTRUMENT VOLTAGE
B
A
GROUND
L1
L2
.25 AMP*
FUSE
Rear View
*Supplied by the customer
8
7
6
5
4
3
2
1
THERMOCOUPLE INPUT
+
-
300 OHMS
MAXIMUM
LEAD
Rear view