890CS & 890CD Common Bus Units
4-50
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames E & F
8
9
10
11
A
B
C
D
1
2
3
5
6
7
E
Control Modes
4-Q
4-Q REGEN
Set-up using 4Q Regen Active Front End (AFE) control mode.
Refer to Chapter 8 to correctly set-up the drive for an 890CD/SD 4-Q Regen
AFE Application.
Autotune is not required.
PMAC
PMAC
Set-up using PMAC (Permanent Magnet AC) servo or torque motor control
mode -
a high performance application where the drive uses Resolver or
Sin/Cos Encoder motor feedback.
In this mode, speed feedback signals from the motor shaft encoder are
processed to determine the rotational speed of the shaft. A PI algorithm within
the software uses this information to produce varying gate drive signals to the
drive circuits. These signals cause the drive to output the required voltage and
frequency for a particular motor speed.
Autotune is not required.
The Motor Selection Wizard in the 890 DSE Configuration Tool
MUST
be
used to correctly set-up the motor and feedback device parameters. Failure to