D-66
Programming
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames E & F
Parameter Descriptions
TIMEOUT
PREF: 29.07
Default: 600.0 s
Range: 0.0 to 600.0 s
Determines the maximum amount of time the sequence is allowed to remain in the low frequency injection braking state.
BASE VOLTS
PREF: 29.08
Default: 100.00 %
Range: 0.00 to 115.47 %
Determines the maximum volts at base speed applied to the motor during injection braking.
ACTIVE
PREF: 29.09
Default: FALSE
Range: FALSE / TRUE
Indicates the state of the Drive. TRUE when injection braking.