E-57
Technical Specifications
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames E & F
890SD Branch Protection Fuses (North America)
It is recommended that UL Listed (JDDZ) non-renewable cartridge fuses, Class K5 or H;
or UL Listed (JDRX) renewable cartridge fuse, Class H, are installed upstream of the
drive.
Model Number
Input Fuse Rating (A)
Model Number
Input Fuse Rating (A)
Constant Torque Quadratic Torque
Constant Torque Quadratic Torque
400VAC BUILD VARIANT
Frame E
Frame F
890SD-432730E
100
110
890SD-433105F
125
175
890SD-432870E
110
125
890SD-433145F
175
200
890SD-433156F
200
225
890SD-433180F
200
225
500VAC BUILD VARIANT
Frame E
Frame F
890SD-532730E
80
90
890SD-533105F
110
150
890SD-532870E
90
110
890SD-533145F
150
175
890SD-533156F
175