MSG11-5715-743/EN: AC20F Series - Hardware Installation Manual
138 (148)
MSG11-5715-743/EN 24.04.2023
Digital Outputs
Terminal Idents:
DX1, DX2, DX3, referenced to 0 V
Nominal Output Voltage:
23 V
Minimum Output
Voltage:
18 V @ 50 mA
Maximum Output
Current:
50mA (Each output, or Total outputs combined)
Isolated:
No
Short Circuit Protection:
Yes
Relay Outputs
Terminal Idents:
RL1A, RL1B, RL2A, RL2B
Maximum Contact
Voltage:
230 VAC (Overvoltage Category II, TN) / 30 VDC
Maximum Contact
Current:
2 Arms
Motor Thermistor Input
Terminal Idents:
TH1, TH2
Compatible Thermistors:
PTC & NTC
Trip Threshold:
Rising resistance: 2500
Ω to 2800 Ω
Falling resistance: 1000
Ω to 1200 Ω
Response Time:
10 secs
Thermistor Self Heating:
<15 mW @ rising resistance threshold
Isolated:
No
– thermistor wiring requires double or reinforced insulation to live
voltages
User +24 V Output
Terminal Idents:
24 V referenced to 0 V
Nominal Output Voltage:
23 V
Minimum Output
Voltage:
20 V @ 50 mA
Maximum Output
Current:
50 mA
Isolated:
No
Over Current Protection:
Yes