MSG11-5715-743/EN: AC20F Series - Hardware Installation Manual
64 (148)
MSG11-5715-743/EN 24.04.2023
3ø, 400 V Products
Frame
Size
Product Code
Motor
Power
(kW)
Inductance
(mH/phase)
Rated Current
(A)
Peak Output
Current (A)
2
20F-42-0040...
1.5
3.676
4.0
7.6
20F-42-0065...
2.2
2.262
6.5
12
20F-42-0090...
4.0
1.634
9.0
17
3
20F-43-0120...
5.5
1.225
12
23
20F-43-0170...
7.5
0.865
17
32
4
20F-44-0230...
11
0.639
23
44
20F-44-0320...
15
0.459
32
61
5
20F-45-0380...
18.5
0.387
38
72
20F-45-0440...
22
0.334
44
84
20F-45-0600...
30
0.245
60
114
6
20F-46-
0750…
37
0.196
75
143
20F-46-
0900…
45
0.163
90
171
7
20F-47-
1100…
55
0.134
110
209
20F-47-
1500…
75
0.098
150
285
8
20F-48-
1800…
90
0.082
180
342
20F-48-
2200…
110
0.067
220
418
20F-48-
2650…
132
0.055
265
504
9
20F-49-
3200…
160
0.046
320
608
10
20F-410-
3600…
180
0.041
360
684
Notes:
-
AC Motor Choke inductance values calculated @400 V, 50 Hz / 480 V, 60 Hz
-
AC Motor Choke impedance is nominally 2 % of drive rating
-
AC Motor Choke maximum voltage rating should be 480 V +10 %, TN/IT
-
AC Motor Choke frequency of operation is 0
– 120 Hz
-
AC Motor Choke inductance at peak current should be >85 % of its nominal value
Calculation
The choke ratings listed above are for guidance only. Customers may want to calculate their own ratings
using the formula below:
𝐿 =
(
𝑉𝑜𝑢𝑡
√3
×
𝑍
100
)
𝐼𝑜𝑢𝑡
÷ (2𝜋 × 𝑓𝑜𝑢𝑡)
Where:
L
= Inductance/phase (H)
Vout
= Line-to-Line Output Voltage (V)
Z
= AC Motor Choke Impedance (%)
Iout
= Rated Output Current (A)
fout
= Output frequency (Hz)