MSG11-5715-743/EN: AC20F Series - Hardware Installation Manual
MSG11-5715-743/EN 24.04.2023
135 (148)
Power Supply = 3ø 380-480 V ±10 %, 50/60 Hz
10 %, PSCC = 5 kA
Motor power, output current and input current must not be exceeded under steady state operating
conditions.
Minimum repetitive power up / power down cycle time = 10 mins.
Frame
Size
Product Code
Motor
Power
(kW)
Output
Current
(A)
Input
Current
(A)
Est. Eff
(%)
Switching
Frequency
(kHz)
nom / max
AC
Current
Derate
(%/kHz)
8
20F-48-
1800…
90
180
190
97
2 / 4
3.0
20F-48-
2200…
110
220
225
97
2 / 4
2.5
20F-48-
2650…
132
265
275
97
2 / 4
5.5
9
20F-49-
3200…
160
320
330
98
2 / 4
6.0
10
20F-410-
3600…
180
360
370
98
2 / 4
7.5
13.2
Internal Brake Switch Ratings
Note: Peak (Instant) = Maximum 20sec, 30% ‘on’ duty (except where this value is the same as the
continuous rating)
Note: Peak (Instant) = Maximum
20sec, 30% ‘on’ duty (except where this value is the same as the
continuous rating)