MSG11-5715-743/EN: AC20F Series - Hardware Installation Manual
MSG11-5715-743/EN 24.04.2023
133 (148)
13
Technical Information
13.1
General Product Ratings
Environment
Operating Temperature:
0 °C to 40 °C (derate output current above 40 °C by 2 % per °C, up to
maximum of 45 °C).
Anybus Comms Option not suitable for use in temperatures >40 °C.
Storage Temperature:
-25 °C to 55 °C
Shipping Temperature:
-25 °C to 70 °C
Altitude:
0
– 1000 m (derate output current above 1000 m by 1 % per 100 m, up to
maximum of 2000 m)
Humidity:
Maximum 90 % relative humidity, non-condensing
Atmosphere:
Non-flammable, non-corrosive, dust free
Chemically Active
Substances:
Complies with C3 according to EN ISO 9223
Vibration & Shock:
Vibration:
-
10
– 57 Hz: Amplitude to 0.075 mm
-
57
– 150 Hz: Acceleration to 10 m/s²
Shock:
-
5 g for 30 msec
Product Enclosure
Rating:
IP20 panel mount (UL: open-type).
Safety
Overvoltage Category:
III (Control Module User Relay terminals: RL1A, RL1B, RL2A & RL2B are
category II (230 V TN))
Pollution Degree:
II (non-conductive pollution, except for temporary condensation)
North America / Canada:
Complies with the requirements of UL61800-5-1 as an open-type drive
Earthing
Earthing:
Permanent earthing is mandatory for product installation:
-
Use a copper productive earth conductor with a minimum 10mm²
cross-sectional area or, where not possible, install a 2
nd
conductor
to a separate earth terminal.
-
The earth conductor must meet local requirements for a protective
earth conductor.
Earth Leakage Current:
>10 mA (all models)
Mains Supply
Input Supply Details (TN
& IT):
Products are suitable for use on TN supplies, with the exception of TN
corner earthed distribution systems.
Products are suitable for use on IT supplies when all Y-Cap & VDR
connections to earth are removed.
Prospective Short
Circuit Current (PSCC):
50 kA: All models when fitted with specified UL fusing
5 kA: All models when
not
fitted with specified UL fusing. Line currents
are specified at this supply rating.
AC Line Fed Power Stack Ratings