Getting Started
1-1
650G AC Drive
Chapter 1
G
ETTING
S
TARTED
Introduction
The 650G Series AC Drive provides simple, compact, and low-cost speed control for 3-phase
induction motors
This manual describes the low-power end of the 650G product range for the following motor
power ratings:
Nominal Input Voltage
Phase
Drive Power
Frame 1
230V
1
0.25 – 0.75kW
0.3 - 1.0 Hp
Frame 2
230V
1
1.1 – 1.5kW
1.5 - 2.0 Hp
Frame 2
400V
3
0.37 – 2.2kW
0.5 - 3.0 Hp
Frame 3
230V
1
2.2kW
3.0 Hp
Frame 3
230V
3
2.2 - 4.0 kW
3.0 - 5.0 Hp
Frame 3
400V
3
3.0 – 7.5kW
4.0 - 10.0 Hp
The drive features:
•
Local or Remote mode operation
•
SELV control terminals (Safe Extra Low Volts)
•
Intelligent monitoring strategy to avoid nuisance tripping
•
In-built protection of the unit against overloads, excessive voltages, phase-to-phase and
phase-to-earth short circuits
•
An internal RFI filter is fitted as standard
•
An internal dynamic brake switch for connection to an external resistor (Frame 3: 230V, and
400V units only)
•
Quiet operation
•
Controlling the unit locally using the 6511 Keypad gives access to parameters, diagnostic
messages, trip settings and for full application programming a connection to a pc is required
along with the drive software tool. Other features also become available, such as the
advanced sensorless vector control scheme which gives high torque, low speed operation;
selectable switching frequencies; and a unique Quiet Pattern control system that minimises
audible noise from the motor.
Note:
Do not attempt to control motors whose rated current is less than 50% of the drive rated
current. Poor motor control or Autotune problems may occur if you do
Equipment Inspection
•
Check for signs of transit damage
•
Check the drive is suitable for your requirements by reading the Product Code on the rating
label. Refer to Chapter 9: “Technical Specifications” - Understanding the Product Code.
If the unit is damaged, refer to Chapter 8: “Routine Maintenance and Repair” for information on
returning damaged goods.
Storage and Packaging
Save the packaging in case of return. Improper packaging can result in transit damage.
If the unit is not being installed immediately, store the unit in a well-ventilated place away from
high temperatures, humidity, dust or metal particles.
About this Manual
This manual is intended for use by the installer, user and programmer of the drive. It assumes a
reasonable level of understanding in these three disciplines.
Note:
Please read all Safety Information before proceeding with the installation and operation
of this unit.
It is important that you pass the manual on to any new user of this unit.