Applications
650G AC Drive
Application 3: Preset Speeds
This is ideal for applications requiring multiple discrete speed levels.
The setpoint is selected from either the sum of the analogue inputs, (as in Application 1 and known here as PRESET 0), or
as one of up to seven other pre-defined speed levels. These are selected using DIN2, DIN3 and DIN4, refer to the Truth
Table below.
Edit parameters AP2 to AP8 on the keypad to re-define the speed levels of PRESET 1 to PRESET 7. Reverse direction is
achieved by entering a negative speed setpoint.
Preset Speed Truth Table
DIN4
DIN3
DIN2
Preset
0V
0V
0V
0
0V
0V
24V
1
0V
24V
0V
2
0V
24V
24V
3
24V
0V
0V
4
24V
0V
24V
5
24V
24V
0V
6
24V
24V
24V
7
= 0
= 3
= 1
Speed
User Relay
RL1A
RL1B
9
8
7
6
5
4
3
2
1
11
WIRE
SINGLE
STARTING
see truth table below
see truth table below
24V = run forward
DOUT3 ( relay)
Control
Terminal
24V = coast to stop, 0 V = drive may run
see truth table below
Setpoint
Speed Trim
DEMAND (0 V = 0%, 10V = 100%)
4 mA = 0%, 20 mA = 100% ( Preset 0 )
0 V = 0%, 10V = 100% ( Preset 0)
RELAY
SOURCE
HEALTH i.e . 0 V = not healthy
= 1
default source
A or V
= 4-20m A
10
9
8
7
6
5
4
3
2
1
13
12
11
DIN7 (ENCB)
DIN6 (ENCA)
DIN5
DIN4
DIN3
DIN2
DIN1
+24V
AOUT1
AOUT2
AIN2
AIN1
0V
unused
unused
COAST STOP
PRESET SELECT 3
PRESET SELECT 2
PRESET SELECT 1
RUN FORWARD
24V
RAMP OUTPUT
+10V REF
SPEED TRIM
SPEED SETPOINT
0V
5
AOP1
5
Ip23
5
IP13
5
dOP3