6-1
Programming Your Application
650G AC Drive
Chapter 6
P
ROGRAMMING
Y
OUR
A
PPLICATION
You can program the drive to your specific application. This programming simply involves
changing parameter values. For instance, parameter
P
1 selects various Applications which can
be used as starting points for application-specific programming.
Each Application internally re-wires the drive for a different use when it is loaded. The default
for the parameter is "1". Changing this parameter's setting to "2" will load Application 2. Refer
to Chapter 12: “Applications” for further information.
If necessary, there are three parameters for tuning your drive. Refer to PID - Tuning Your Drive,
page 6-14.
Saving Your Modifications
When parameter values are modified or an Application is loaded, the new settings are saved
automatically. The drive will retain the new settings during power-down.
MMI Parameters
This table provides information about each parameter accessible using the keypad, or MMI
(Man Machine Interface). For more information about these and additional parameters
accessible using DSE Lite (or other suitable programming tool), refer to the 650G Software
Product Manual on our website: www.parker.com/ssd
Key to MMI Parameters Table
F
Parameters indicated with
F
are visible with full menus only. Refer to the
DETAILED MENUS parameter (
ST
99).
M
Parameters indicated with
M
are Motor Parameters. They are not reset by changing
Application using parameter
P
1; all other parameters are reset to default values.
VF
Parameters indicated with
VF
are only visible when the drive is in VF (Volts/Hz)
motor control mode, as selected by parameter
S
CL01.
SV
Parameters indicated with
SV
are only visible when the drive is in SV (Sensorless
Vector) motor control mode, as selected by parameter
S
CL01.
Note:
The “Range” for a parameter value is given in the Configurable Parameters Table.
Ranges for outputs are given as “—.xx %”, for example, indicating an indeterminate
integer for the value, to two decimal places.
MMI Parameters Table
MMI Parameters Table
Display
Parameter
Description
Range
Default
SET::PAR Menu
APPLICATION
This parameter selects and loads the Application to
be used. APP 0 will not control a motor. APP 6, 7 &
8 are for future use. You can edit an Application in
DSE Lite and, then set this parameter to CUSTOM
to produce your own custom Application.
Refer to the 650G Software Product Manual,
Chapter 5: "Applications" which gives detailed
information about each Application.
Note:
Parameter values are changed to
factory settings by loading a new
Application, except Motor Parameters
(indicated
M
)
0= NULL
1= STANDARD
2= LOCAL/REM
(AUTO/MANUAL)
3= PRESETS
4= RAISE/LOWER
5= PID
6= AUXILLARY
COMMS
7= APP 7
8= APP 8
9= CUSTOM
1
MAX SPEED
M
The frequency at which the 650G will run when
maximum setpoint is applied. The default is
Product Code dependent
7.5 to 300Hz
50 or
60Hz