12-13
Applications
650G AC Drive
Application 6: AUXILLIARY COMMS
General purpose implementation of basic speed control, with sequencing and speed reference
conveniently controlled and monitored (via just 3 parameters) over comms.
AP01 (Tag 599)
Mask
Function
Bit 4
Jog
Bit 3
Trip reset
Bit 2
Reverse
Bit 1
Enable
Bit 0
Run forward
AP03 (Tag 598)
Mask
Diagnostic
Bit 13
At speed
Bit 12
Zero speed
Bit 11
Ramping
Bit 10
Fan running
Bit 9
Healthy
Bit 8
Reversed
Bit 7
System reset
Bit 6
Ready
Bit 5
Switched on
Bit 4
Switch on enabled
Bit 3
Stopping
Bit 2
Jogging
Bit 1
Running
Bit 0
Tripped
10k Speed
Setpoint
User Relay
10
9
8
7
6
5
4
3
2
1
RL1A
RL1B
13
12
11
COAST STOP
OVERRIDE
DIN7 ( ENCB)
DIN6 ( ENCA)
DIN5
COAST STOP
DIN4
DIN3
DIN2
DIN1
+24V
AOUT1
RAMP OUTPUT
DEMAND (0 V = 0%, 10 V = 100%)
AOUT2
AIN2
SPEED TRIM 1
4 mA = 0%, 20 mA = 100%
AIN1
SPEED TRIM2
0 V = 0%, 10V = 100%
0V
DOUT3
RELAY SOURCE
HEALTH i.e. 0 V = not healthy
24V
+10 V REF
0V
not used
Control
Terminal
= 0
= 3
= 1
= 1
default source
A or V
= 4- 20mA
5
IP23
5
OPO1
5
IP13
5
OP31
not used