EMC - Requirement
638A
638B
EMC – Emission
(Conducted)
EMC – Emission
(Radiated)
EN 61 800-3
First Environment C1
First Environment C2
Second Environment C3
EN 61 800-3
First Environment C1
First Environment C2
Second Environment C3
max. Motor cable length
20m
1)
40m
2)
20m
20m
EMC – Immunity
Levels
EN 61800-3
(include EN 50081-2
and EN 50082-2)
3)
meet
meet
3)
meet
meet
EMC – Emission
(Conducted)
EN 61 800-3
First Environment C1
First Environment C2
Second Environment C3
Minimum standards for the Second
Environment are kept to.
1)
for max. 100m motor cable length, use the drive with Option A (less leakage current) and
the external filter Type LNF RA *230/12.
2)
With external Filter of the Serie LNFB, is a groupe RFI suppression for max. 4 Device with a
overall
Motor cable length of 60m, possible.
3)
For the operation in the first environment with unlimited availability is a cabinet damping of at least
10 dB in the frequency range of 30-1000MHz necessary.
11.2
Conditions of utilization for UL certification 638A
Temperature rating of field installed conductors shall be at least 60°C. Use copper
Conductors only.
Suitable for use on a circuit capable of delivering not more than 5000 rms symmetrical
amperes, 240V ac maximum when protected by Branch circuit protection as below.
These Device needs Branch Circuit Protection (BCP) with the following nominal fuse ratings:
Model Number
Nominal Fuse Ratings
638A-01-3
6A
638A-02-3
6A
638A-04-3
10A
638A-06-3
15A
PARKER Hannifin recommends:
UL listed (JDDZ) Fusible cut-out Class K5, Class H Class J or Class CC, or UL listed (JDRX)
renewable cartridgefuse Class H rated.
The maximum surrounding air temperature is 40°C.
The drive provides internal motor overload protection.
This must be set so that 200% of the nominal motor current is not exceeded.
Integral solid state short circuit protection does not provide branch circuit protection.
Branch circuit protection must be provided in accordance with the National Electric Code and
any additional local codes.
Aux. Control circuits for connection to “class 2” power supply only.
The device are only to be installed in a degree of contamination 2 environment (maximum).