Operation manual of solar controller SR658
Page 78 of 105
MXSFS
60
℃
0.5-95
℃
0.5
℃
Maximum temperature of heated tank
MNSFO
60
℃
0.5-89.5
℃
0.5
℃
Minimum temperature of solid fuel boiler
TIMER
OFF
ON/OFF
Timer function
t 1O
00:00
00:00-23:59
Start time of the first time-section
t 1F
00:00
00:00-23:59
Close time of the first time- section
t 2O
00:00
00:00-23:59
Start time of the second time-section
t 2F
00:00
00:00-23:59
Close time of the second first time-
section
t 3O
00:00
00:00-23:59
Start time of the third time-section
t 3F
00:00
00:00-23:59
Close time of the third time- section
AH
OFF
ON/OFF
Thermostat function
AHS
T3
T2/T3/T4
Target sensor for thermostat function
AHO
40
℃
0.0-95
℃
0.5
℃
Switch-on temperature
AHF
45
℃
0.0-94.5
℃
0.5
℃
Switch-off temperature
t A1O
00:00
00:00-23:59
Start time of the first time-section
t A1F
23:59
00:00-23:59
Close time of the first time- section
t A2O
00:00
00:00-23:59
Start time of the second time-section
t A2F
00:00
00:00-23:59
Close time of the second first time-
section
t A3O
00:00
00:00-23:59
Start time of the third time-section
t A3F
00:00
00:00-23:59
Close time of the third time- section
BEEP
OFF
ON/OFF
Beeper warning function
(
sensor error
,
no flow
)
Function set:
SFB Solid fuel boiler function set
►Press “SET” button to select main menu “AUX”
►Press “SET” button, “SFB” displays on the screen
►Press “SET” button, “SFB OFF” displays on the screen
►Press “SET” button, “OFF” blinks on the screen
►Press “↑”, “↓” button, to activate this function
“SFB ON” displays on the screen
►Press “SET” or “ESC” button, to confirm the setting
►Press “↑” button, “DTSFO 6K” displays on the screen
►Press “SET” button, “6K” blinks on the screen
►Press “↑”, “↓” button, to adjust the switch-on temperature difference
►Press “SET” or “ESC” button, to confirm the setting
►Press “↑” button, “DTSFF 4K” displays on the screen
►Press “SET” button, “4K” blinks on the screen