Operation manual of solar controller SR658
Page 85 of 105
►Press “SET” button, “70
o
C
” blinks on the screen
►Press “↑”, “↓” button, to adjust disinfection heating temperature
►Press “SET” or “ESC” button, to confirm the setting
►Press “↑” button, “SDIS 18:00” displays on the screen
►Press “SET” button, hour “18” blinks on the screen
►Press “↑”, “↓” button, to adjust the start time of disinfection function
►Press “SET” or “ESC” button, to confirm the setting
(
21
)
OPARR Parallel relay
Function description:
With this function, e. g. a valve can be controlled in parallel to the pump via a separate relay.
If solar loading takes place (R1 and / or R2) or if a solar function is active, the selected
parallel relay will be energized too. The parallel relay can also energize the parallel pump
inversely
Note:
If R1 and / or R2 is in
manual mode, then its parallel relay won’t be energized.
When
display on the screen, it’s mean that the function is activate, if the icon
flash, it’s mean that the functions is running.
INVE OFF means R1 triggered, parallel reply also triggered.
INVE ON, means R1 ceased, parallel reply is switched-off
Manu structure
Main menu
Submenu
Default
set
Adjust range
Description
Main menu
OPARR
OFF
ON/OFF
Parallel relay on/ off
PARRE
R5
R2, R3, R4,
R5
Selection a parallel relay
(if one output is already used, then
this output can’t be selected)
INVE
OFF
ON/OFF
Parallel relay logic on/off