Operation manual of solar controller SR658
Page 46 of 105
Main
menu
Submen
u 1
Submen
u 2
Default set
Adjust range
Adjust
step
Main menu
CIRC
DHW circuit function
TCYC
OFF
ON/OFF
ON/OFF
DHW
circuit
function
TEMP
OFF
ON/OFF
Temperature control the
DHW circuit pump
CYCFS
ON
ON/OFF
Flow control the DHW circuit
pump
STAT
ON
ON/OFF
Trigger condition of DHW
circuit pump
Tank temperature (T3 or T2)
is 2
o
C higher than the
switch-off temperature
CYCO
40
℃
/3min
5-53
℃
/1-30min
0.5
℃
/1min
Switch-on temperature or
running time
CYCF
45
℃
/15min
7-55
℃
/0-60min
0.5
℃
/1min
Switch-off temperature or
the rest time
t C1O
05:00
00:00-23:59
Start time of the first time-
section
t C1F
07:00
00:00-23:59
Close time of the first time-
section
t C2O
11:00
00:00-23:59
Start time of the second
time- section
t C2F
13:00
00:00-23:59
Close time of the second
time - section
t C3O
17:00
00:00-23:59
Start time of the third time-
section
t C3F
22:00
00:00-23:59
Close time of the third time -
section
Function set:
(take DHW three time - sections temperature control mode as example)
►Press “SET” button, select main menu CIRC
►Press “SET” button, “TCYC” displays on the screen
►Press “SET” button, “TCYC OFF” displays
►Press “SET” button, “OFF” blinks
►Press “↑”, “↓” button to activate the function, “TCYC ON” displays on the screen
►Press “SET” or “ESC” button, to confirm the setting
►Press “↑”, “TEMP OFF” displays on the screen (three time - sections temperature control)
►Press “SET” button, “OFF” blinks
►Press “↑”, “↓” button to activate the function, “TEMP ON” displays on the screen
►Press “SET” or “ESC” button, to confirm the setting