58
Aquarea air-to-water heat pumps - Planning and installation manual - 02/2022
Product Description
4
Mono-bloc systems | Aquarea T-CAP | H Generation | Single Phase / Three Phase | Heating and
Cooling | R410A
Single phase
Three phase
Outdoor unit
WH‑MXC09H3E5
WH‑MXC12H6E5
WH‑MXC09H3E8
WH‑MXC12H9E8
WH‑MXC16H9E8
Heating capacity / COP (A +7 °C, W 35 °C)
kW / –
9.00 / 4.84
12.00 / 4.74
9.00 / 4.84
12.00 / 4.74
16.00 / 4.28
Heating capacity / COP (A +7 °C, W 55 °C)
kW / –
9.00 / 2.94
12.00 / 2.88
9.00 / 2.94
12.00 / 2.88
16.00 / 2.71
Heating capacity / COP (A +2 °C, W 35 °C)
kW / –
9.00 / 3.59
12.00 / 3.44
9.00 / 3.59
12.00 / 3.44
16.00 / 3.10
Heating capacity / COP (A +2 °C, W 55 °C)
kW / –
9.00 / 2.21
12.00 / 2.19
9.00 / 2.21
12.00 / 2.19
16.00 / 2.13
Heating capacity / COP (A -7 °C, W 35 °C)
kW / –
9.00 / 2.85
12.00 / 2.72
9.00 / 2.85
12.00 / 2.72
16.00 / 2.49
Heating capacity / COP (A -7 °C, W 55 °C)
kW / –
9.00 / 2.02
12.00 / 1.92
9.00 / 2.02
12.00 / 1.92
16.00 / 1.86
Cooling capacity / EER (A 35 °C, W 7 °C)
kW / –
7.00 / 3.17
10.00 / 2.81
7.00 / 3.17
10.00 / 2.81
12.20 / 2.56
Cooling capacity / EER (A 35 °C, W 18 °C)
kW / –
7.00 / 5.19
10.00 / 5.13
7.00 / 5.19
10.00 / 5.13
12.20 / 3.49
ErP data for Space Heating
Average climate
Seasonal energy efficiency (ηs,h)
W35 / W55
%
181 / 130
170 / 130
181 / 130
170 / 130
160 / 125
SCOP
W35 / W55
4.59 / 3.32
4.32 / 3.32
4.59 / 3.32
4.32 / 3.32
4.08 / 3.20
Energy class
1
W35 / W55
A+++ / A++
A++ / A++
A+++ / A++
A++ / A++
A++ / A++
Warm climate
Seasonal energy efficiency (ηs,h)
W35 / W55
%
235 / 158
231 / 158
235 / 158
231 / 158
231 / 159
SCOP
W35 / W55
5.95 / 4.03
5.86 / 4.02
5.95 / 4.02
5.86 / 4.02
5.86 / 4.05
Energy class
1
W35 / W55
A+++ / A+++
A+++ / A+++
A+++ / A+++
A+++ / A+++
A+++ / A+++
Cold climate
Seasonal energy efficiency (ηs,h)
W35 / W55
%
160 / 125
160 / 125
160 / 125
160 / 125
150 / 125
SCOP
W35 / W55
4.08 / 3.20
4.08 / 3.20
4.08 / 3.20
4.08 / 3.20
3.83 / 3.20
Energy class
1
W35 / W55
A++ / A++
A++ / A++
A++ / A++
A++ / A++
A++ / A++
Sound power
2
Heat
dB(A)
65
65
65
65
66
Dimension
H x W x D
mm
1,410 x 1,283 x 320
1,410 x 1,283 x 320
1,410 x 1,283 x 320
1,410 x 1,283 x 320
1,410 x 1,283 x 320
Net weight
kg
142
142
151
151
164
Refrigerant (R410A) / CO
2
Eq.
3
kg / t
2.30 / 4.802
2.30 / 4.802
2.30 / 4.802
2.30 / 4.802
2.35 / 4.907
Water pipe connector
Inch
R 1¼
R 1¼
R 1¼
R 1¼
R 1¼
Pump
Number of speeds
Variable Speed
Variable Speed
Variable Speed
Variable Speed
Variable Speed
Input power (Min / Max)
W
32 / 102
34 / 110
32 / 102
34 / 110
38 / 120
Heating water flow (∆T=5 K. 35 °C)
l/min
25.8
34.4
25.8
34.4
45.9
Capacity of integrated electric heater
kW
3
6
3
9
9
Input power
Heat
kW
1.86
2.53
1.86
2.53
3.74
Cool
kW
2.21
3.56
2.21
3.56
4.76
Running and starting
current
Heat
A
8.8
11.7
3.0
4.0
5.7
Cool
A
10.4
16.5
3.5
5.3
7.1
Current 1
A
29.0
29.0
14.7
11.9
15.5
Current 2
A
13.0
26.0
13.0
13.0
13.0
Recommended fuse
A
30 / 30
30 / 30
16 / 16
16 / 16
16 / 16
Recommended cable size, supply 1 / 2
mm²
3 x 4.0 or 6.0 / 3 x 4.0
3 x 4.0 or 6.0 / 3 x 4.0
5 x 1.5 / 3 x 1.5
5 x 1.5 / 5 x 1.5
5 x 1.5 / 5 x 1.5
Operation range
Outdoor ambient
Heat
°C
-20 ~ +35
-20 ~ +35
-20 ~ +35
-20 ~ +35
-20 ~ +35
Cool
°C
+16 ~ +43
+16 ~ +43
+16 ~ +43
+16 ~ +43
+16 ~ +43
Water outlet
Heat
°C
20 ~ 60
20 ~ 60
20 ~ 60
20 ~ 60
20 ~ 60
Cool
°C
5 ~ 20
5 ~ 20
5 ~ 20
5 ~ 20
5 ~ 20
1 Scale from A+++ to D.
2 Sound power in accordance to 811/2013, 813/2013 and EN12102-1:2017 at +7 °C.
3 WH-MXC models are hermetically sealed.
Note: