45
Aquarea air-to-water heat pumps - Planning and installation manual - 02/2022
Product Description
4
All in One systems | Aquarea T-CAP | H Generation | Three Phase | Super Quiet | Heating and
Cooling | R410A
Three phase (Power to indoor)
Kit
KIT‑AQC09HE8
KIT‑AQC12HE8
KIT‑AQC16HE8
Heating capacity / COP (A +7 °C, W 35 °C)
kW / –
9.00 / 4.84
12.00 / 4.74
16.00 / 4.28
Heating capacity / COP (A +7 °C, W 55 °C)
kW / –
9.00 / 2.94
12.00 / 2.88
16.00 / 2.71
Heating capacity / COP (A +2 °C, W 35 °C)
kW / –
9.00 / 3.59
12.00 / 3.44
16.00 / 3.10
Heating capacity / COP (A +2 °C, W 55 °C)
kW / –
9.00 / 2.21
12.00 / 2.19
16.00 / 2.13
Heating capacity / COP (A -7 °C, W 35 °C)
kW / –
9.00 / 2.85
12.00 / 2.72
16.00 / 2.49
Heating capacity / COP (A -7 °C, W 55 °C)
kW / –
9.00 / 2.02
12.00 / 1.92
16.00 / 1.86
Cooling capacity / EER (A 35 °C, W 7 °C)
kW / –
7.00 / 3.17
10.00 / 2.81
12.20 / 2.57
Cooling capacity / EER (A 35 °C, W 18 °C)
kW / –
7.00 / 5.19
10.00 / 5.13
12.20 / 3.49
ErP data for Space Heating
Average climate
Seasonal energy efficiency (ηs,h)
W35 / W55
%
181 / 130
170 / 130
160 / 125
SCOP
W35 / W55
4.59 / 3.32
4.32 / 3.32
4.08 / 3.20
Energy class
1
W35 / W55
A+++ / A++
A++ / A++
A++ / A++
Warm climate
Seasonal energy efficiency (ηs,h)
W35 / W55
%
235 / 158
231 / 158
231 / 159
SCOP
W35 / W55
5.95 / 4.02
5.86 / 4.02
5.86 / 4.05
Energy class
1
W35 / W55
A+++ / A+++
A+++ / A+++
A+++ / A+++
Cold climate
Seasonal energy efficiency (ηs,h)
W35 / W55
%
160 / 125
160 / 125
150 / 125
SCOP
W35 / W55
4.08 / 3.20
4.08 / 3.20
3.83 / 3.20
Energy class
1
W35 / W55
A++ / A++
A++ / A++
A++ / A++
Indoor unit
WH‑ADC0916H9E8
WH‑ADC0916H9E8
WH‑ADC0916H9E8
Sound pressure
Heat / Cool
dB(A)
33 / 33
33 / 33
33 / 33
Dimension
H x W x D
mm
1,800 x 598 x 717
1,800 x 598 x 717
1,800 x 598 x 717
Net weight
kg
126
126
126
Water pipe connector
Inch
R 1¼
R 1¼
R 1¼
A class pump
Number of speeds
Variable Speed
Variable Speed
Variable Speed
Input power (Min / Max)
W
36 / 152
36 / 152
36 / 152
Heating water flow (∆T=5 K. 35 °C)
l/min
25.8
34.4
45.9
Capacity of integrated electric heater
kW
9
9
9
Recommended fuse
A
16 / 16
16 / 16
16 / 16
Recommended cable size, supply 1 / 2
mm²
5 x 1.5 / 5 x 1.5
5 x 1.5 / 5 x 1.5
5 x 1.5 / 5 x 1.5
Water volume
l
185
185
185
Maximum water temperature
°C
65
65
65
Material inside tank
Stainless steel
Stainless steel
Stainless steel
Tapping profile according EN16147
L
L
L
ErP data for Water Heating
Average climate
Seasonal energy efficiency (ηw,h)
%
95
95
91
SCOP
2.37
2.37
2.27
Energy class
2
A
A
A
Warm climate
Seasonal energy efficiency (ηw,h)
%
110
110
107
SCOP
2.75
2.75
2.67
Energy class
2
A
A
A
Cold climate
Seasonal energy efficiency (ηw,h)
%
75
75
72
SCOP
1.87
1.87
1.80
Energy class
2
A
A
B
Outdoor unit
WH‑UQ09HE8
WH‑UQ12HE8
WH‑UQ16HE8
Sound power
3
Heat
dB(A)
58
58
62
Dimension / Net weight H x W x D
mm / kg
1,410 x 1,283 x 320 / 151
1,410 x 1,283 x 320 / 151
1,410 x 1,283 x 320 / 161
Refrigerant (R410A) / CO
2
Eq.
kg / t
2.85 / 5.951
2.85 / 5.951
2.99 / 6.243
Pipe diameter
Liquid / Gas
Inch (mm)
3/8 (9.52) / 5/8 (15.88)
3/8 (9.52) / 5/8 (15.88)
3/8 (9.52) / 5/8 (15.88)
Pipe length range / Elevation difference (in/out)
m / m
3 ~ 30 / 20
3 ~ 30 / 20
3 ~ 30 / 20
Pipe length for additional gas / Additional gas amount
m / g/m
10 / 50
10 / 50
10 / 50
Operation range
Outdoor ambient
Heat
°C
-28 ~ +35
-28 ~ +35
-28 ~ +35
Cool
°C
+16 ~ +43
+16 ~ +43
+16 ~ +43
Water outlet
Heat
°C
20 ~ 60
20 ~ 60
20 ~ 60
Cool
°C
5 ~ 20
5 ~ 20
5 ~ 20
1 Scale from A+++ to D.
2 Scale from A+ to F.
3 Sound power in accordance to 811/2013, 813/2013 and EN12102-1:2017 at +7 °C.
Notes:
EER and COP calculation is based in accordance to EN14511.
This product is designed to comply with the European Water Quality Directive 98/83/EC amended by 2015/1787/EU. The lifespan of the product is not guaranteed in the case of the use of
groundwater, such as spring water or well water, the use of tap water when salt or other impurities are contained, nor in areas of acidic water quality. Maintenance and warranty costs related to
these cases are the customer’s responsibility.