42
Aquarea air-to-water heat pumps - Planning and installation manual - 02/2022
Product Description
4
All in One Compact systems | Aquarea High Performance | J Generation | Single Phase | Heating and
Cooling | R32
Single phase (Power to indoor)
Kit
KIT‑ADC03JE5C
KIT‑ADC05JE5C
KIT‑ADC07JE5C
KIT‑ADC09JE5C‑1
Heating capacity / COP (A +7 °C, W 35 °C)
kW / –
3.20 / 5.33
5.00 / 5.00
7.00 / 4.76
9.00 / 4.48
Heating capacity / COP (A +7 °C, W 55 °C)
kW / –
3.20 / 2.81
5.00 / 2.72
7.00 / 2.82
8.95 / 2.78
Heating capacity / COP (A +2 °C, W 35 °C)
kW / –
3.20 / 3.64
4.20 / 3.18
6.85 / 3.41
7.00 / 3.40
Heating capacity / COP (A +2 °C, W 55 °C)
kW / –
3.20 / 2.19
4.10 / 1.99
6.20 / 2.21
6.30 / 2.16
Heating capacity / COP (A -7 °C, W 35 °C)
kW / –
3.30 / 2.80
4.20 / 2.59
5.60 / 2.87
6.12 / 2.78
Heating capacity / COP (A -7 °C, W 55 °C)
kW / –
3.20 / 1.79
3.55 / 1.71
5.25 / 1.94
5.90 / 1.93
Cooling capacity / EER (A 35 °C, W 7 °C)
kW / –
3.20 / 3.52
4.50 / 3.00
6.70 / 3.03
8.20 / 2.72
Cooling capacity / EER (A 35 °C, W 18 °C)
kW / –
3.20 / 4.71
4.80 / 4.29
6.70 / 4.72
9.00 / 4.18
ErP data for Space Heating
Average climate
Seasonal energy efficiency (ηs,h)
W35 / W55
%
200 / 136
200 / 136
193 / 130
193 / 130
SCOP
W35 / W55
5.07 / 3.47
5.07 / 3.47
4.90 / 3.32
4.90 / 3.32
Energy class
1
W35 / W55
A+++ / A++
A+++ / A++
A+++ / A++
A+++ / A++
Warm climate
Seasonal energy efficiency (ηs,h)
W35 / W55
%
245 / 165
245 / 165
227 / 160
227 / 160
SCOP
W35 / W55
6.20 / 4.20
6.20 / 4.20
5.75 / 4.07
5.75 / 4.07
Energy class
1
W35 / W55
A+++ / A+++
A+++ / A+++
A+++ / A+++
A+++ / A+++
Cold climate
Seasonal energy efficiency (ηs,h)
W35 / W55
%
157 / 110
157 / 110
164 / 116
164 / 116
SCOP
W35 / W55
4.00 / 2.83
4.00 / 2.83
4.18 / 2.98
4.18 / 2.98
Energy class
1
W35 / W55
A++ / A+
A++ / A+
A++ / A+
A++ / A+
Indoor unit
WH‑ADC0309J3E5C
WH‑ADC0309J3E5C
WH‑ADC0309J3E5C
WH‑ADC0309J3E5C
Sound pressure
Heat / Cool
dB(A)
28 / 28
28 / 28
28 / 28
28 / 28
Dimension
H x W x D
mm
1,640 x 598 x 600
1,640 x 598 x 600
1,640 x 598 x 600
1,640 x 598 x 600
Net weight
kg
101
101
101
101
Water pipe connector
Inch
R 1¼
R 1¼
R 1¼
R 1¼
A class pump
Number of speeds
Variable Speed
Variable Speed
Variable Speed
Variable Speed
Input power (Min / Max)
W
30 / 120
30 / 120
30 / 120
30 / 120
Heating water flow (∆T=5 K. 35 °C)
l/min
9.20
14.30
20.10
25.80
Capacity of integrated electric heater
kW
3.00
3.00
3.00
3.00
Recommended fuse
A
16 / 16
16 / 16
25 / 16
25 / 16
Recommended cable size, supply 1 / 2
mm²
3 x 1.5 / 3 x 1.5
3 x 1.5 / 3 x 1.5
3 x 2.5 / 3 x 1.5
3 x 2.5 / 3 x 1.5
Water volume
l
185
185
185
185
Maximum water temperature
°C
65
65
65
65
Material inside tank
Stainless steel
Stainless steel
Stainless steel
Stainless steel
Tapping profile according EN16147
L
L
L
L
ErP data for Water Heating
Average climate
Seasonal energy efficiency (ηw,h)
%
128
128
116
116
SCOP
3.20
3.20
2.90
2.90
Energy class
2
A+
A+
A+
A+
Warm climate
Seasonal energy efficiency (ηw,h)
%
154
154
134
134
SCOP
3.86
3.86
3.35
3.35
Energy class
2
A+
A+
A+
A+
Cold climate
Seasonal energy efficiency (ηw,h)
%
99
99
98
98
SCOP
2.48
2.48
2.45
2.45
Energy class
2
A
A
A
A
Outdoor unit
WH‑UD03JE5
WH‑UD05JE5
WH‑UD07JE5
WH‑UD09JE5‑1
Sound power
3
Heat
dB(A)
55
55
59
59
Dimension / Net weight H x W x D
mm / kg
622 x 824 x 298 / 37
622 x 824 x 298 / 37
795 x 875 x 320 / 61
795 x 875 x 320 / 61
Refrigerant (R32) / CO
2
Eq.
kg / T
0.9 / 0.608
0.9 / 0.608
1.27 / 0.857
1.27 / 0.857
Pipe diameter
Liquid / Gas
Inch (mm)
1/4 (6.35) / 1/2 (12.70)
1/4 (6.35) / 1/2 (12.70)
1/4 (6.35) / 5/8 (15.88)
1/4 (6.35) / 5/8 (15.88)
Pipe length range / Elevation difference (in/out)
m / m
3 ~ 25 / 20
3 ~ 25 / 20
3 ~ 50 / 30
3 ~ 50 / 30
Pipe length for additional gas / Additional gas amount
m / g/m
10 / 20
10 / 20
10 / 25
10 / 25
Operation range
Outdoor ambient
Heat
°C
-20 ~ +35
-20 ~ +35
-20 ~ +35
-20 ~ +35
Cool
°C
+10 ~ +43
+10 ~ +43
+10 ~ +43
+10 ~ +43
Water outlet
Heat
°C
20 ~ 60
20 ~ 60
20 ~ 60
20 ~ 60
Cool
°C
5 ~ 20
5 ~ 20
5 ~ 20
5 ~ 20
1 Scale from A+++ to D.
2 Scale from A+ to F.
3 Sound power in accordance to 811/2013, 813/2013 and EN12102-1:2017 at +7 °C.
Notes:
EER and COP calculation is based in accordance to EN14511.
This product is designed to comply with the European Water Quality Directive 98/83/EC amended by 2015/1787/EU. The lifespan of the product is not guaranteed in the case of the use of
groundwater, such as spring water or well water, the use of tap water when salt or other impurities are contained, nor in areas of acidic water quality. Maintenance and warranty costs related to
these cases are the customer’s responsibility.