VRF SYSTEMS Indoor Unit
2 - 4
2
1. Room Temperature Control
Intake Air Temperature Control
< FRESH AIR INTAKE MODE (Type E2) >
This product brings outdoor fresh air into the building and adjusts and supplies the air with nearly current indoor temperature.
Automatic cooling and heating operation mode
Due to the temperature difference between the outdoor air and preset temperature in remote controller, cooling or heating
operation can be automatically selected.
In the case of group control, the setting is possible when all of the indoor units in the same refrigerant circuit consist of one
group.
Cooling operation mode
: In case that the outdoor temperature is 5°C higher than the preset temperature in remote
controller.
Fan operation mode
: In case that the outdoor temperature and preset temperature in remote controller are within
±5°C.
Heating operation mode
: In case that the outdoor temperature is 5°C lower than the preset temperature in remote
controller.
Example: In case that the preset temperature in remote controller set at 20°C
(43)
40
30
10
0
20
)
5
–
(
)
5
–
(
15
25
(+5)
Outdoor temperature (°C)
Heating operation mode
Discharge temperature
setting at 45°C
Cooling operation
mode
Discharge temperature
setting at 18°C
Fan operation
mode
Discharge
temperature
setting in a
range of
15 - 25°C
Cooling operation mode
It is recommended that the temperature setting in remote controller be more than 24°C.
If the intake air temperature is getting higher than the preset temperature in remote controller, the unit operates in cooling
mode. On the contrary, if the intake air temperature becomes lower than the preset temperature, the unit operates in fan
mode.
Heating operation mode
It is recommended that the temperature setting in remote controller be set at 16°C.
If the intake air temperature is getting lower than the preset temperature in remote controller, the unit operates in heating
mode. On the contrary, if the intake air temperature becomes higher than the preset temperature, the unit operates in fan
mode.
Fan operation mode
In the moderate climates, supply of fresh outdoor air can provide as passive cooling.
NOTE
In general, it is recommended that you set in the automatic cooling and heating operation mode.
IO̲00̲280020̲all.indb 7
2013/12/18 16:12:48
②
③
①
②
③
①
SM830232-02_欧州向けVRF Indoor SM&TRSM.indb 4
17/03/09 13:53:16
Summary of Contents for S-22MF2E5A8
Page 8: ...vii MEMO SM830232 02_ VRF Indoor SM TRSM indb 7 17 02 02 13 07 38...
Page 10: ...MEMO 1 2 SM830232 02_ VRF Indoor SM TRSM indb 2 2017 02 01 13 57 51...
Page 32: ...MEMO 2 22 SM830232 02_ VRF Indoor SM TRSM indb 22 17 03 09 13 53 31...
Page 34: ...MEMO 3 2 SM830232 02_ VRF Indoor SM TRSM indb 2 2017 02 01 13 58 57...
Page 36: ...MEMO 4 2 SM830232 02_ VRF Indoor SM TRSM indb 2 2017 02 01 14 07 36...
Page 94: ...MEMO 5 58 SM830232 02_ VRF Indoor SM TRSM indb 58 17 03 08 18 34 10...
Page 96: ...MEMO 6 2 SM830232 02_ VRF Indoor SM TRSM indb 2 17 03 09 9 50 49...
Page 102: ...201703 SM830232 02_ VRF Indoor SM TRSM indb 1 2017 02 01 14 11 24...