2 - 15
VRF SYSTEMS Indoor Unit
2
16. Indoor Unit Control PCB
【
LEAD pb
】
FREE SOLDERING
12 13
1FA4B1B108000-4
14
4
A747337
A
73
C
1FA4B1B108000-4
A747337 A73C
Indoor heat
exchanger
(E3) sensor
EEPROM
1. Wall Mounted (Type K2) CR-22MK2E5 : S-15MK2E5A / S-22MK2E5A / 28MK2E5A / 36MK2E5A
Indoor Unit Control PCB Switches and Functions
Indoor unit control PCB
T10:
6P plug (yellow):
Used for remote control. (Refer to the remote control section.)
(CN061)
Control items: (1) Start/stop input
(2) Remote controller prohibit input
(3) Start signal output
(4) Alarm signal output
EXCT:
2P plug (red):
Can be used for demand control. When input is present, forces the unit to operate with the thermostat
OFF.
DISP:
(CN072)
2P plug (white):
(CN063)
2P plug (black) Type T2, F2, U1:
(CN062)
6P plug (black) 3-4pin Type U2 only:
(CN062)
6P plug (black) 5-6pin Type U2 only:
Short-circuiting this plug allows the unit to be operated by the remote controller, even if it is not
connected to an outdoor unit.
(In this case, alarm "E04," which indicates trouble in the serial communication between the indoor
and outdoor unit, does not occur.)
CHK:
(CN071)
2P plug (white):
(CN062)
2P plug (black) Type T2, F2, U1:
Test pin. Short-circuiting this pin allows the indoor FM (H fan speed), drain pump, flap motor
(F1 position), and electronic expansion valve full-open position to be checked.
However this function turns OFF if the indoor unit protection mechanism is activated.
The unit can be operated even if the remote controller and outdoor unit are not connected.
However even if the remote controller cannot is connected, it cannot be used to operate the unit.
This function can be used for short-term tests.
JP1:
Jumper wire:
Allows selection of the T10 terminal start/stop signal. (Refer to the remote control section.)
Status at shipment : Pulse signal
Jumper wire cut : Static signal (continuous signal)
FAN DRIVE 2P plug (white):
This terminal sends a signal to the ventilation fan when the FAN button on the wired remote
controller is used to operate a commercially-available ventilation fan.
(Refer to the remote control section.)
Use a ventilation fan which can accept no-voltage A contact as the external input signal.
Power LED: LED (red):
Illuminates when power is supplied. Blinks when there is a failure in the EEPROM (IC10: nonvolatile
memory).
EEPROM: Nonvolatile memory:
Memory which stores the unit type data and other information.
When the PCB is replaced, remove the EEPROM from the old PCB and install it onto the
new PCB.
If an IC failure occurs, replace with a new IC which was provided with the service PCB,
and set the necessary information from the wired remote controller.
(For the procedure, refer to the servicing technical materials.)
The indoor unit power terminal plate may be a 7P type, 6P type or may be a 5P type. (Refer to the figure at below.)
The basic wiring diagram shows the 7P-type terminal plate.
Therefore the terminal plate may differ from the illustrations.
(CN073)
(J001)
(IC010)
(CN032)
(D002)
5P terminal board
Power
supply
Type K1
Type U2
Type K2
6P terminal board
Power
supply
Inter-unit
control
wiring
Inter-unit
control
wiring
Remote con-
trol wiring
Remote
control
wiring
Power
supply
Inter-unit
control
wiring
Remote
control
wiring
Type Y2
Type E2
Terminal Board
Power supply
cable
Inter-unit con-
trol wiring
L
N
U1 U2 R1 R2
6P terminal board
6P terminal board
Type F2, T2, U1
Power
supply
Remote
control
wiring
Inter-unit
control
wiring
L
N
U1 U2 R1 R2
Type M1
Power
supply
Remote
control
wiring
Inter-unit
control
wiring
L
N
U1
U2
R1
R2
L
N
U1 U2
7P terminal board
U1
U2
R2
R1
L
N
4P terminal board
2P terminal board
Unit
control
line
Remote
control
line
Power
supply
TD831172-04 VRF SYS INDOOR.indb 2
17/01/12 20:12:49
SM830232-02_欧州向けVRF Indoor SM&TRSM.indb 15
17/03/09 13:53:20
Summary of Contents for S-22MF2E5A8
Page 8: ...vii MEMO SM830232 02_ VRF Indoor SM TRSM indb 7 17 02 02 13 07 38...
Page 10: ...MEMO 1 2 SM830232 02_ VRF Indoor SM TRSM indb 2 2017 02 01 13 57 51...
Page 32: ...MEMO 2 22 SM830232 02_ VRF Indoor SM TRSM indb 22 17 03 09 13 53 31...
Page 34: ...MEMO 3 2 SM830232 02_ VRF Indoor SM TRSM indb 2 2017 02 01 13 58 57...
Page 36: ...MEMO 4 2 SM830232 02_ VRF Indoor SM TRSM indb 2 2017 02 01 14 07 36...
Page 94: ...MEMO 5 58 SM830232 02_ VRF Indoor SM TRSM indb 58 17 03 08 18 34 10...
Page 96: ...MEMO 6 2 SM830232 02_ VRF Indoor SM TRSM indb 2 17 03 09 9 50 49...
Page 102: ...201703 SM830232 02_ VRF Indoor SM TRSM indb 1 2017 02 01 14 11 24...