5 - 27
2. Detailed Settings Function
5
VRF SYSTEMS Indoor Unit
ExTERNAL STATIC PRESSURE SETTINg
•
Low Silhouette Ducted (S-15~160MF2E5A / S-15~160MF2E5A8)
Choose one of the following methods from “a”, “b”, “c” or “d” as shown in the flow chart (within the dotted lines) and then make the
setting accordingly.
a. No setting modification............................................................ : Use-as-is at shipment (there are cases in which the setting may differ
from the shipment setting when reset after once setting the external
static pressure.)
b. Manual setting (set with the PC board) ................................... : For high static pressure. Switching method with the short-circuit
connector.
c. Manual setting (set with the wired remote controller) ............. : Low static pressure ~ high static pressure
d. Auto airflow volume setting (set on the wired remote controller) .... : Air outlet volume is automatically adjusted to the rated airflow volume
with the auto airflow control drive.
Flow of External Static Pressure
Finish the ducting and electrical wiring and prepare it for use. (Note (1))
External static pressure should be set during initial operations after installation (before
the cooling and heating test run).
When operating with group control (connecting multiple indoor units with one wired
remote controller), make the low silhouette ducted type to the main unit.
Start external static pressure setting
a. No setting modification
b. Manual setting
(set with the PC board)
TP3 or TP1 short-circuit
Refer to section “1-1. How to
Set on PC Board”.
c. Manual setting
Item code “b0” : 0~15 setting
(*Note (3)) (* Note (4))
Refer to section 1-2 or 1-3.
d. Auto airflow volume setting
(* Note (4)) Item code “b0” :
-2 setting
Refer to section 1-2 or 1-3.
Operation checks for external static pressure settings (*Note (2))
Refer to section 1-2 or 1-3.
Check if the setting is within the range of use on the PQ diagram.
If out of range, adjust until it becomes within the range of use.
This can be omitted if deemed unnecessary in the event of the same installation/set-up being available.
Auto airflow volume control
operations (*Note (5))
Refer to section 1-2 or 1-3.
Test operation display will disappear. (*Note (6))
External static pressure setting completed
Wired remote controller available
Lines
15
and
14
settings (high static pressure) on
the PQ diagram required
Set the rated airflow
volume with the exception of lines
15
,
14
and
8
Line
8
(set at ship-
ment) on the PQ diagram de-
signed and installed
No
No
No
No
Yes
Yes
Yes
Yes
NOTE
(1) Check the following items before performing the setting-check operations or auto airflow volume operations.
1) Check to make sure that the electrical wiring and ducting have been completed. Activate the stand-by mode. In particular, make
sure that the closed damper located in the middle of the duct is open, if installed. Also, make sure that air filters have been
installed inside the air inlet duct.
Check to make sure air is not leaking from the joints.
2) If multiple air outlets and air inlets are included, adjust the airflow volume ratio of all of them until they meet the design airflow ratio.
3) Make sure the address setting has been completed.
(2) The operation check will be completed in approximately three minutes if the settings have been made correctly. The settings will be
modified if they are out of the range of use (maximum 30 minutes). If this is not completed within 31 minutes, check whether the air
speed is set to “H” or not.
SM830232-02_欧州向けVRF Indoor SM&TRSM.indb 27
17/03/08 18:33:50
Summary of Contents for S-22MF2E5A8
Page 8: ...vii MEMO SM830232 02_ VRF Indoor SM TRSM indb 7 17 02 02 13 07 38...
Page 10: ...MEMO 1 2 SM830232 02_ VRF Indoor SM TRSM indb 2 2017 02 01 13 57 51...
Page 32: ...MEMO 2 22 SM830232 02_ VRF Indoor SM TRSM indb 22 17 03 09 13 53 31...
Page 34: ...MEMO 3 2 SM830232 02_ VRF Indoor SM TRSM indb 2 2017 02 01 13 58 57...
Page 36: ...MEMO 4 2 SM830232 02_ VRF Indoor SM TRSM indb 2 2017 02 01 14 07 36...
Page 94: ...MEMO 5 58 SM830232 02_ VRF Indoor SM TRSM indb 58 17 03 08 18 34 10...
Page 96: ...MEMO 6 2 SM830232 02_ VRF Indoor SM TRSM indb 2 17 03 09 9 50 49...
Page 102: ...201703 SM830232 02_ VRF Indoor SM TRSM indb 1 2017 02 01 14 11 24...