5 - 39
2. Detailed Settings Function
5
VRF SYSTEMS Indoor Unit
•
Slim Low Static Ducted (S-15~56MM1E5A)
Choose one of the methods (selection of “a”, “b”, “c” within the range of dotted line as shown in the flowchart below)
and make settings.
a. No setting changes:
When using as it is factory preset at shipment.
(If resetting after external static pressure setting once, it might be different from factory preset.)
b. Manual setting (on PCB):
This is static pressure setting excepting factory preset at shipment. Dip switch select method.
c. Manual setting (by wired remote controller):
Static pressure setting excepting factory preset at shipment.
Flow of External Static Pressure
NOTE
(1) Refer to Table 2-13, 2-14, 2-15 and Fig. 2-13 for details on the relationship between the value of item code “5d” and the external
static pressure.
(2) When set in group control (connecting multiple indoor units with one wired remote controller), set each indoor unit to item code “5d”.
When amending the setting after selecting [ b. Manual setting] (due to airflow path changes, etc.), it is necessary to cancel [b.
Manual setting] (switching OFF positions).
When [b. Manual setting] has not been cancelled, [c. Manual setting] will be activated if selected, but [b. Manual setting] takes
precedence when the power is switched back on after power outages, etc.
CAUTION
l
Make sure the external static pressure is in a range of specifications.
Then proceed the external static pressure setting.
Improper settings can cause noise, a shortage of airflow volume and water leakage.
Refer to Fig. 2-13 for the external static pressure setting range.
l
Be sure to set the [External Static Pressure Setting] once again after amending the airflow path
for the duct or air outlet after setting the external static pressure.
Start of external static pressure setting
Is it designed and
installed at the setting line
at shipment
on PQ line drawing?
Operating by
wired remote
controller
Selection methods
of external static
pressure setting
No
No
Yes
Yes
a. No setting changes
b. Manual setting
(Setting on PCB)
Setting switches of TP3
Refer to section "1-1. How to
set on PC Board".
c. Manual setting
Item code 5d : Setting 3
(*Note 1) (*Note 2)
Refer to section 1-2., 1-3. or 1-4.
Completion of external static pressure setting
SM830232-02_欧州向けVRF Indoor SM&TRSM.indb 39
17/03/08 18:34:01
Summary of Contents for S-22MF2E5A8
Page 8: ...vii MEMO SM830232 02_ VRF Indoor SM TRSM indb 7 17 02 02 13 07 38...
Page 10: ...MEMO 1 2 SM830232 02_ VRF Indoor SM TRSM indb 2 2017 02 01 13 57 51...
Page 32: ...MEMO 2 22 SM830232 02_ VRF Indoor SM TRSM indb 22 17 03 09 13 53 31...
Page 34: ...MEMO 3 2 SM830232 02_ VRF Indoor SM TRSM indb 2 2017 02 01 13 58 57...
Page 36: ...MEMO 4 2 SM830232 02_ VRF Indoor SM TRSM indb 2 2017 02 01 14 07 36...
Page 94: ...MEMO 5 58 SM830232 02_ VRF Indoor SM TRSM indb 58 17 03 08 18 34 10...
Page 96: ...MEMO 6 2 SM830232 02_ VRF Indoor SM TRSM indb 2 17 03 09 9 50 49...
Page 102: ...201703 SM830232 02_ VRF Indoor SM TRSM indb 1 2017 02 01 14 11 24...