VRF SYSTEMS Indoor Unit
2
2. Heating Standby
2. Heating Standby
In heating mode, the indoor fan speed decreases to prevent cold air discharge from the indoor unit. During this
time, (heating standby) is displayed on the remote controller.
①
This condition occurs in the following cases.
・
Thermostat OFF
・
Defrosting operation
・
Indoor heat exchanger liquid temperature (E1) < 28˚C and discharge air temperature < 25˚C just after
heating operation started
The fan speed may sometimes increase when this condition continues for 6 minutes.
②
The fan mode increases when the heat exchanger liquid temperature (E1) or discharge air
temperature increases.
The fan mode is selected based on the discharge air temperature and E1 temperature as shown
in the below figure. If the E1 temperature and discharge air temperature are different, the higher
temperature is used.
The function of "HH" is identical to the automatic fan speed mode.
Operation
Discharge air
E1
32
Temprature (
)
30
28
26
20
16
29
27
25
23
17
13
*HH
STOP
L
STOP
STOP
LL
LL
STOP
STOP
LL
LL
L
L
L
L
H
LL L H
L
H
L
HH
L
H
Set
fan
STOP
LL
L
H
H
speed
Operation
Discharge air
E1
Temprature (
)
26
20
16
1
0
-1
STOP
STOP
H
fan speed
< FRESH AIR INTAKE MODE (Type E2) >
SM830232-02_欧州向けVRF Indoor SM&TRSM.indb 5
17/03/09 13:53:17
Summary of Contents for S-22MF2E5A8
Page 8: ...vii MEMO SM830232 02_ VRF Indoor SM TRSM indb 7 17 02 02 13 07 38...
Page 10: ...MEMO 1 2 SM830232 02_ VRF Indoor SM TRSM indb 2 2017 02 01 13 57 51...
Page 32: ...MEMO 2 22 SM830232 02_ VRF Indoor SM TRSM indb 22 17 03 09 13 53 31...
Page 34: ...MEMO 3 2 SM830232 02_ VRF Indoor SM TRSM indb 2 2017 02 01 13 58 57...
Page 36: ...MEMO 4 2 SM830232 02_ VRF Indoor SM TRSM indb 2 2017 02 01 14 07 36...
Page 94: ...MEMO 5 58 SM830232 02_ VRF Indoor SM TRSM indb 58 17 03 08 18 34 10...
Page 96: ...MEMO 6 2 SM830232 02_ VRF Indoor SM TRSM indb 2 17 03 09 9 50 49...
Page 102: ...201703 SM830232 02_ VRF Indoor SM TRSM indb 1 2017 02 01 14 11 24...