5 - 44
3. Remote Controller Servicing Functions
5
VRF SYSTEMS Indoor Unit
•
The remote controller includes a number of servicing functions. Use these as needed for test runs and inspections.
■
Timer Remote Controller CZ-RTC2
Fig. 3-1
List of Servicing Functions
Functions
Description
Button operation
Reset operation
Unit status
Test run
Operation with forced
thermostat ON
Press and hold the
button for 4
seconds or longer.
Press the
button.
Current operation is
maintained.
Sensor
temperature
display
Temperature display
from each sensor
Press and hold the
and
buttons for 4 seconds or longer.
Servicing
check display
Alarm history display
Press and hold the
and
buttons for 4 seconds or longer.
Simple
settings
Filter lifetime, operating
mode priority, central
control address, and
other settings
Press and hold the
and
buttons for 4 seconds or longer.
When settings
are made from a
remote controller,
the indoor unit
where that remote
controller is
connected stops.
Detailed
settings
System address, indoor
unit address, central
control address, and
other settings
Press and hold the
,
and
buttons for 4 seconds or longer.
Automatic
address
Automatic address
setting based on
command from the
wired remote controller
Press and hold the
and the
timer operation
buttons for 4
seconds or longer.
Automatic reset
Entire system
stops.
Address
change
Change of indoor unit
address
Press and hold the
and the
timer operation
buttons for 4
seconds or longer.
Press the
button.
SM830231-00̲Single̲欧州.indb 17
2014/04/04 13:48:33
Functions
Description
Menu selection
Reset operation
Unit status
■
High-spec Wired Remote Controller CZ-RTC3 / CZ-RTC5A
Display of "maintenance function" screen
1
Keep pressing the
,
and
buttons simultaneously for 4 or more seconds.
The “Maintenance func” screen appears on the
LCD display.
2
Press the
or
button to see each
menu.
If you wish to see the next screen instantly, press
the
or
button.
Fig. 3-2
List of Servicing Functions
Test run
ECONAVI
・
CZ-KPU3A
・
CZ-CENSC1
Operation with forced
Display from each sensor
thermostat ON
4. Test run
0. ECONAVI info.
Press the
button.
Press the
button.
Sensor temperature
display
Temperature display from
each sensor
5. Sensor info
Servicing check
display
Alarm history display
6. Service check
Display status of nanoe™ X
Simple settings
Filter lifetime, operating
mode priority, central control
address, and other settings
7. Simple settings
Press the
button.
(Restart)
When settings are
made from a remote
controller, the indoor
unit where that
remote controller is
connected stops.
Detailed settings
System address, indoor
unit address, central control
address, and other settings
8. Detailed settings
13. nanoe
Automatic address
Automatic address setting
based on command from the
wired remote controller
9. Auto address
Automatic reset
Entire system stops.
SM830231-00̲Single̲欧州.indb 18
2014/04/04 13:48:34
Maintenance func
1. Outdoor unit error data
2. Service contact
3. RC setting mode
4.Test run
Sel.
Page [
] Confirm
20:30 (THU)
nanoe™ X
(CZ-RTC5A only)
SM830232-02_欧州向けVRF Indoor SM&TRSM.indb 44
17/03/08 18:34:06
Summary of Contents for S-22MF2E5A8
Page 8: ...vii MEMO SM830232 02_ VRF Indoor SM TRSM indb 7 17 02 02 13 07 38...
Page 10: ...MEMO 1 2 SM830232 02_ VRF Indoor SM TRSM indb 2 2017 02 01 13 57 51...
Page 32: ...MEMO 2 22 SM830232 02_ VRF Indoor SM TRSM indb 22 17 03 09 13 53 31...
Page 34: ...MEMO 3 2 SM830232 02_ VRF Indoor SM TRSM indb 2 2017 02 01 13 58 57...
Page 36: ...MEMO 4 2 SM830232 02_ VRF Indoor SM TRSM indb 2 2017 02 01 14 07 36...
Page 94: ...MEMO 5 58 SM830232 02_ VRF Indoor SM TRSM indb 58 17 03 08 18 34 10...
Page 96: ...MEMO 6 2 SM830232 02_ VRF Indoor SM TRSM indb 2 17 03 09 9 50 49...
Page 102: ...201703 SM830232 02_ VRF Indoor SM TRSM indb 1 2017 02 01 14 11 24...