5 - 11
2. Detailed Settings Function
5
VRF SYSTEMS Indoor Unit
<Procedure of CZ-RTC3 / CZ-RTC5A>
Fig. 2-2
1
Keep pressing the
,
and
buttons
simultaneously for 4 or more seconds.
The “Maintenance func” screen appears on the
LCD display.
2
Press the
or
button to see each
menu.
If you wish to see the next screen instantly, press
the
or
button.
Select “8. Detailed settings” on the LCD display
and press the
button.
The “Detailed settings” screen appears on the
LCD display.
Select the “Unit no.” by pressing the
or
button for changes.
Maintenance func
5. Sensor info.
6. Servicing check
8. Detailed settings
Sel.
Page [
] Confirm
20:30 (THU)
7. Simple settings
Detailed settings
Unit no.
Code no.
Set data
10
3-1
0001
Sel.
Next
20:30 (THU)
3
Select the “Code no.” by pressing the
or
button.
Change the “Code no.” by pressing the
or
button (or keeping it pressed).
4
Select the “Set data” by pressing the
or
button.
Select one of the “Set data” by pressing the
or
button.
Then press the
button.
5
Select the “Unit no.” by pressing the
or
button and press the
button.
The “Exit detailed settings and restart?” (Detailed
setting-end) screen appears on the LCD display.
Select “YES” and press the
button.
Detailed settings
Unit no.
Code no.
Set data
3-1
0001
Sel.
Next
20:30 (THU)
10
Detailed settings
Unit no.
Code no.
Set data
3-1
Sel.
20:30 (THU)
10
0001
Detailed settings
Unit no.
Code no.
Set data
ALL
Sel.
Next
20:30 (THU)
01
0002
Exit detailed settings
and restart?
NO
YES
SM830231-00̲Single̲欧州.indb 6
2014/04/04 13:48:32
START
[ ]
20:30 (THU)
Maintenance func
1. Outdoor unit error data
2. Service contact
3. RC setting mode
4.Test run
Sel.
Page [
] Confirm
20:30 (THU)
[
] Confirm
<Procedure of CZ-RTC4>
1 Press and hold the
and
,
buttons
simultaneously for 4 seconds or longer.
2 “
”, unit No. “
”, item code “
”, and
settings data “
” are displayed blinking on the
remote controller LCD display (Fig. 2-3). At this time,
the indoor unit fan begins operating.
3 If group control is in effect, press the
select the address (unit No.) of the indoor unit to set.
At this time, the fan at the indoor unit begins operating.
button and
*If unit No. “
” is displayed, the same setting
will be made for all indoor units.
4 Press the temperature setting
/
select the item code to change.
buttons to
5 Press the timer time
/
buttons to select the
desired setting data.
*For item codes and setting data, see the following
page.
6 Press the
button. (The display stops blinking
and remains lit, and setting is completed.)
7 Press the
button to return to normal remote
controller display.
Fig. 2-3
A
°
°
7
6
3
2
5
4
1
SM830232-02_欧州向けVRF Indoor SM&TRSM.indb 11
17/03/08 18:33:44
Summary of Contents for S-22MF2E5A8
Page 8: ...vii MEMO SM830232 02_ VRF Indoor SM TRSM indb 7 17 02 02 13 07 38...
Page 10: ...MEMO 1 2 SM830232 02_ VRF Indoor SM TRSM indb 2 2017 02 01 13 57 51...
Page 32: ...MEMO 2 22 SM830232 02_ VRF Indoor SM TRSM indb 22 17 03 09 13 53 31...
Page 34: ...MEMO 3 2 SM830232 02_ VRF Indoor SM TRSM indb 2 2017 02 01 13 58 57...
Page 36: ...MEMO 4 2 SM830232 02_ VRF Indoor SM TRSM indb 2 2017 02 01 14 07 36...
Page 94: ...MEMO 5 58 SM830232 02_ VRF Indoor SM TRSM indb 58 17 03 08 18 34 10...
Page 96: ...MEMO 6 2 SM830232 02_ VRF Indoor SM TRSM indb 2 17 03 09 9 50 49...
Page 102: ...201703 SM830232 02_ VRF Indoor SM TRSM indb 1 2017 02 01 14 11 24...