Selecting the DC fan motor tap (when setting from the PCB)
4-Way Cassette type (Type U1)
<Procedure> Stop the system before performing these steps.
Open the electrical component box cover, then check the indoor unit control PCB. (Fig. 2-5)
Setting No. (3) :
Setting No. (6) :
Connect the jumper connector (2P: yellow) which was supplied with the accessory to the correct connector pin
on the indoor unit control PCB according to the setting number which was confirmed in Table for DC Fan Motor
Tap Settings.
Then connect the jumper connector to the connector pin TP3 (2P: yellow) on the indoor unit control PCB.
Then connect the jumper connector to the connector pin TP6 (2P: white) on the indoor unit control PCB.
Fig. 2-5
Fig. 2-6
FAN-TAP
TP
6
TP
3
TP
1
(WHT
)
YEL
RE
D
Ceiling type
<Procedure> Stop the system before performing these steps.
4-Way Cassette type (Type U2)
<Procedure> Stop the system before performing these steps.
Open the electrical component box cover, then check the indoor unit control PCB. (Fig. 2-6)
Connect the jumper connector (2P: yellow) which was supplied with the accessory to the correct connector pin on
the indoor unit control PCB according to the setting number which was confirmed in Table 2-2 (Table of DC Fan
Motor Tap Settings).
If the setting No. is (1), then connect the jumper connector to the connector pin TP1 (2P: red) on the indoor unit con-
trol PCB.
If the setting No. is (3), then connect the jumper connector to the connector pin TP3 (2P: yellow) on the indoor unit
control PCB.
Open the electrical component box cover, then check the indoor unit control PCB. (Fig. 2-6)
Change the DIP switch on the indoor unit control PCB in accordance with the setting number which was
confirmed in Table for DC Fan Motor Tap Settings.
TP
6
TP
3
TP
1
1
ON
2 3
TP6
TP3
TP1
1 2 3
ON
Setting example
1: OFF
2: OFF
3: ON
Setting No.
DIP switch
(1)
TP
6
TP
3
TP
1
1 2 3
ON
(6)
ON
1 2 3
TP
6
TP
3
TP
1
(3)
ON
1 2 3
TP
6
TP
3
TP
1
SM830232-02_欧州向けVRF Indoor SM&TRSM.indb 26
17/03/08 18:33:50
Summary of Contents for S-22MF2E5A8
Page 8: ...vii MEMO SM830232 02_ VRF Indoor SM TRSM indb 7 17 02 02 13 07 38...
Page 10: ...MEMO 1 2 SM830232 02_ VRF Indoor SM TRSM indb 2 2017 02 01 13 57 51...
Page 32: ...MEMO 2 22 SM830232 02_ VRF Indoor SM TRSM indb 22 17 03 09 13 53 31...
Page 34: ...MEMO 3 2 SM830232 02_ VRF Indoor SM TRSM indb 2 2017 02 01 13 58 57...
Page 36: ...MEMO 4 2 SM830232 02_ VRF Indoor SM TRSM indb 2 2017 02 01 14 07 36...
Page 94: ...MEMO 5 58 SM830232 02_ VRF Indoor SM TRSM indb 58 17 03 08 18 34 10...
Page 96: ...MEMO 6 2 SM830232 02_ VRF Indoor SM TRSM indb 2 17 03 09 9 50 49...
Page 102: ...201703 SM830232 02_ VRF Indoor SM TRSM indb 1 2017 02 01 14 11 24...