2 - 3
VRF SYSTEMS Indoor Unit
2
1. Room Temperature Control
Remote controller sensor is enabled
Set temp. in remote
controller
28
℃
28
℃
28
℃
Detected temp. by
sensor
30.0
℃
27.5
℃
27.0
℃
Detected temp. by
body sensor
30.0
℃
27.5
℃
27.0
℃
Detected temp. by
remote controller
sensor
30.0
℃
27.5
℃
27.0
℃
Room temp. = temp.
detected by remote
controller sensor
30.0
℃
=30.0
27.5
℃
=27.5
27.0
℃
=27.0
T
+2.0deg -0.5deg -1.0deg
Thermostat
ON
Thermostat
OFF
Thermostat
OFF
Remote controller sensor is enabled
Set temp. in remote
controller
20
℃
20
℃
20
℃
Detected temp. by
sensor
17.0
℃
20.5
℃
21.0
℃
Detected temp. by
body sensor
21.0
℃
24.5
℃
25.0
℃
Detected temp. by
remote controller
sensor
17.0
℃
20.5
℃
21.0
℃
Room temp. = temp.
detected by remote
controller sensor
17.0
℃
=17.0
20.5
℃
=20.5
21.0
℃
=21.0
T
+3.0deg -0.5deg -1.0deg
Thermostat
ON
Thermostat
OFF
Thermostat
OFF
①
The thermostat does not turn OFF for 3 minutes after it turns ON.
②
The thermostat does not turn ON 1 to 3 minutes after it turns OFF.
③
The thermostat does not turn OFF for 60 minutes during the test run mode. (Forced thermostat ON)
*However, the thermostat turns OFF if an alarm occurs.
ON
ON
OFF
Set temp.
Set temp.
Set temp.
Set temp.
-1
+1
+2
(deg)
ON
ON
OFF
+1
+2
-1
(deg)
ON
ON
OFF
-1
+1
+2
(deg)
Heating
ON
ON
OFF
+1
+2
-1
(deg)
Body sensor is enabled
Remote controller sensor is enabled
-0.5
-0.5
Room temp.
Cooling
Room temp.
Cooling
Heating
Room temp.
Room temp.
Thermostat
Thermostat
Thermostat
Thermostat
SM830232-02_欧州向けVRF Indoor SM&TRSM.indb 3
17/03/09 13:53:16
Summary of Contents for S-22MF2E5A8
Page 8: ...vii MEMO SM830232 02_ VRF Indoor SM TRSM indb 7 17 02 02 13 07 38...
Page 10: ...MEMO 1 2 SM830232 02_ VRF Indoor SM TRSM indb 2 2017 02 01 13 57 51...
Page 32: ...MEMO 2 22 SM830232 02_ VRF Indoor SM TRSM indb 22 17 03 09 13 53 31...
Page 34: ...MEMO 3 2 SM830232 02_ VRF Indoor SM TRSM indb 2 2017 02 01 13 58 57...
Page 36: ...MEMO 4 2 SM830232 02_ VRF Indoor SM TRSM indb 2 2017 02 01 14 07 36...
Page 94: ...MEMO 5 58 SM830232 02_ VRF Indoor SM TRSM indb 58 17 03 08 18 34 10...
Page 96: ...MEMO 6 2 SM830232 02_ VRF Indoor SM TRSM indb 2 17 03 09 9 50 49...
Page 102: ...201703 SM830232 02_ VRF Indoor SM TRSM indb 1 2017 02 01 14 11 24...