Panasonic Electric Works Nordic AB
MEW01351
Rev: -
Planning Instructions Fire alarm system EBL512 G3, V1.1.x
79
23
Routing equipment output (Fire brigade tx) is disabled.
72
24
The specified zone is disabled.
25
The specified alarm point (zone/address) is disabled.
26
One or more alarm points (zone/address) are disabled.
76
27
One or more faults are generated in the system.
73
28
Loss of mains (in a c.i.e. or external power supply 3366).
NOTE!
The output(s) will be activated immediately but
the corresponding fault is normally delayed (set via
WinG3).
29
This control expression is true for 5 seconds, whenever a
reset pulse is sent to the specified zone/address. The
control expression can only be used in the same c.i.e. as
the specified zone/address.
30
The programmed time channel (1-63) is activated.
31
Alert annunciation activated (by any alarm point set to
activate this function).
74
For more information, see
EBL512 G3 Operating Instructions MEW01163.
32
Alert annunciation activated (by any alarm point set to
activate this function)
74
and acknowledged. For more
information, see EBL512 G3 Operating Instructions
MEW01163.
33
Door open in any control unit in the system.
75
34
General Key cabinet alarm activated. For more
information, see EBL512 G3 Operating Instructions
MEW01163.
35
This control expression is true when all control outputs of
the types
Control
,
Fire ventilation
and
Extinguishing
in
all control units are disabled via menu H2/B7.
76
This
output shall be type Control – neutral.
36
This control expression is true when all control outputs of
type
Alarm device
are disabled via menu H2/B8
77
. This
output shall be type Control – neutral.
37
This trigger condition plus the OR operator shall be used
for each detector (zone-address) controlling a fire door
(normally > two detectors). Type of output is normally
71
Indicated by LED
Routing equipment
"Fault tx activated". Output can be
tested via menu H1.
72
Indicated by LED
Fault/Disablements
"Fire brigade tx".
73
Indicated by LED
Fault / Disablements
"General fault" and/or LED
Routing equipment
"Fault tx activated".
74
Valid until the AA alarm is reset or becomes a normal fire alarm.
75
Or ext FBPs connected to the control unit(s).
Indicated by the "Door open" symbol in the display symbol area.
76
Indicated by LED
Fault / Disablements
"General Disablements".
77
Indicated by LED
Fault / Disablements
"Alarm devices".