86
Buzzer
checked = activated interlocking input will turn on the c.i.e.
buzzer (0.8 / 0.8 sec.)
81
. The buzzer can be silenced. It will be
automatically turned on again, if a new interlocking input is activated.
Latched output
checked = Output reset has to be performed via menu
H9/C3. (Automatically output reset will not take place when the
control expression becomes false.).
Fault
checked = Fault detection ON.
Fault Detection Time
: If the input is not activated within 5-255
seconds after the output is activated
82
, a fault will be generated:
FAULT: Interlocking input AAA/PP
14.2
Interlocking indications
One or more activated Interlocking Combinations (interlocking output
and/or input) are indicated in the c.i.e. display
83
:
Interlocking input/output activated
See menu H9/C1
Disabled interlocking output is indicated by the LED "Disablements".
14.3
Information of interlocking combinations
(H9)
Menu H9 has the following sub menus.
14.3.1
Display interlocking information (H9/C1)
See also chapter "Interlocking indications", page 86.
In menu H9/C1 will information be shown as follows:
Output AAA/PP activated at HH:MM
User definable text message.. .. ..
or
Output AAA/PP act HH:MM, input act
HH:MM
User definable text message.. .. ..
or
Input AAA/PP activated at HH:MM
User definable text message.. .. ..
AAA = Interlocking combination Area
PP = Interlocking combination Point within the Area
HH = Hours
MM = Minutes
81
Priority order: Fire alarm – Pre-warning - Interlocking - Fault.
82
After the end of the any delay time.
83
This indication has the lowest priority and will only be shown if the
display was empty.