Planning Instructions Fire alarm system EBL512 G3, V1.1.x
161
Item
C.i.e.
System
General fire alarm via progr. input
250
External fault via progr. input
50
Programmable outputs (= control
expressions)
148
512
Addressable 2 voltage outputs unit
3364
40
Interlocking Combinations
200
1000
149
Presentation numbers / alarm points
150
that can be presented in the display(s)
in case of fire alarm
512
512
Presentation numbers
150
that can be
programmed
512
30 x 512 =
15 360
Zones
151
that can be programmed
512
512
152
Faults
300
Disabled zones
512
Disabled alarm points (zone/address) +
Disabled COM loops
200
153
Disabled outputs
200
154
Disabled interlocking outputs
200
155
Sensors activating SERVICE signal
100
Max. number of AAF zones
(Max. 5 detectors per AAF zone.)
156
100
148
Approx. 4000 trigger conditions can be used in these control expressions.
149
Max. 100 user definable texts can be displayed "at the same time".
150
Presentation number is a ZONE only or ZONE – ADDRESS.
151
Any zone number between 001 and 999 can be used for the 512 zones.
152
Theoretically 999 zones can be programmed but according to EN54-2 it
shall be possible to present all "fire alarms" in the display, i.e. max. 512.
153
Zone/address disabled via time channel not included.
154
Control outputs disabled via menu H2/B7 and Alarm devices disabled via
menu H2/B8 not included.
155
Interlocking outputs disabled via menu H2/B7 not included.
156
Used in conjunction with the AAF Control, which is available on the
Australian market only.