Planning Instructions Fire alarm system EBL512 G3, V1.1.x
39
NOTE!
The COM loop address for the Addressable Base station for
wireless units (4610) is set on a DIL-switch in the unit respectively.
The COM loop address for a wireless detector (4601) is depending on
which Base station it is "connected" to, see chapter "Other COM loop
units", page 51.
9.1.1
Input units
Each COM loop input unit
is added and programmed via WinG3.
Depending on type of unit, regarding:
Technical address (COM loop address) 001-255
Name (normally not changed)
Zone number and Address within the zone
Alarm text (user definable)
Regular Alarm algorithm (some units only)
Options:
Alternative Alarm algorithm & Time Channel (some units only)
Alert annunciation & Time Channel (some units only)
Disablement & Time Channel (some units only)
Two-units-dependent fire alarm, i.e. co-incidence alarm & Time
Channel (some units only)
Delayed (fire alarm)
Quiet alarm (Australian function)
Figure 7. An
example
of a WinG3 dialog box is the "Analog
photo electric smoke detector 4301" dialog box.
For more information, see WinG3 help.
Connections, if nothing else is specified, see drawing 512 G3 - 31.