Planning Instructions Fire alarm system EBL512 G3, V1.1.x
149
COM loop units (input / display units)
Normal state
(quiescent) (mA)
Alarm state
(activated) (mA)
Analog heat detector 3308 + analog base 3312xx
130
0.3
2.3
Analog heat detector, enclosed 3309
130
0.2
1.7
Analog multi detector 4300 + analog base 3312xx
130
0.3
2.3
Analog smoke detector 4301 + analog base 3312xx
130
0.3
2.3
Addressable manual call point 3333 / 3339
2
5
Alarm Acknowledge Facility Control (AAFC)
131
2
5
Addressable base station for wireless units 4610
132
5
5
NOTE!
On each COM loop, up to 5 sensors / detectors can have their LEDs lit at the same time.
COM loop units (output units, etc.)
Normal state
(quiescent) (mA)
Alarm state
(activated) (mA)
Analog base with isolator 4313
133
< 1.3
< 1.3
Addressable multipurpose I/O unit 3361
2.2
max. 12
134
Addressable 2 voltage outputs unit 3364
135
<6
<6
(Addressable) External power supply 3366
<15
<15
Addressable siren 3377
1
max. 13
Addressable sounder base 3379
0.75
max 3
Addressable beacon 4380
1.7
4-5
I/O matrix board 4582
max. 6
max. 6
Fan control application board 4594
136
4-6
4-6
130
Extern LED current consumption. 2218: add 1 mA.
Analog base with isolator 4313 can be used instead of Analog base 3312.
132
24 V DC power supply also required.
132
24 V DC power supply also required.
133
Detector not included.
134
Only if the input In 0 is used as a zone line input, else approx. 2.2 mA.
135
External 24 V DC power supply also required, e.g. the 3366 unit.
136
Two 4594 boards are mounted on a Fan control panel 4594. 24 V DC
power supply also required.