Panasonic Electric Works Nordic AB
MEW01351
Rev: -
Planning Instructions Fire alarm system EBL512 G3, V1.1.x
85
Figure 16. WinG3 "Interlocking Combination" dialog box.
Name
: Displayed in the WinG3 Tree and List views. Default is
"Interlocking Combination" that can be edited when wanted /
required. "Area-Point" will be added in the tree view. "Area-Point"
will be shown under "Zone-Address" in the list view.
The
Available interlocking
outputs
list displays all the previous
programmed outputs, Type = "Interlocking".
The
Available interlocking
inputs
list displays all the previous
programmed inputs, Type "Interlocking". Select one
Output
and one
Input
. Press
Select
and the selected output and input will be shown in
the
Selected output
and
Selected input
field respectively.
It is possible to
Delete
an output / input (from the field).
Output parent:
Shows where the selected output is situated, e.g.
Control unit 0.
Input parent:
Shows where the selected input is situated, e.g.
Control unit 0.
Area
and
Point
: Each "Interlocking Combination" is presented as
Area-Point (compare with Zone-Address). Area numbers 1-999 are
possible and within each Area, Point numbers 1-99 are possible to use.
An Area can only be used in one c.i.e.
Text
= User definable text message to be shown in the menu H9/C1.
Can be written in this field or in the "Texts" dialog box, see chapter
"Creating the alarm texts via WinG3", page 111.