Panasonic Electric Works Nordic AB
MEW01351
Rev: -
Planning Instructions Fire alarm system EBL512 G3, V1.1.x
159
27
Technical data
Voltage
Primary (V AC):
230
(176-264) -- 1.6 A
System (V DC):
24
147
Current consumption (A)
Quiescent / active: Depending on type (5000 or 5001), type and
number of exp. boards, connected external equipment, etc.
See chapter "Current consumption", page 148
Ambient temperature (
o
C)
Operating: 0 to +40
Storage: -40 to +70
Ambient humidity (%RH)
max. 90, non condensing
Ingress protection rating
IP 30
Size H x W x D (mm)
5000: 628 x 438 x 187. See also drawing 512 G3 - 01
5001: 625 x 418 x 177.
Weight (kg)
5000: 20
5001: 19
Colour
5000: Metal cabinet: Aluminium & light grey (NCS S 1500-N / PMS
Cool Gray 2)
5001: Metal cabinet: light grey (NCS S 1500-N / PMS Cool Gray 2)
Approvals
Conforms to EN 54-2 and EN 54-4.
The Swedish front conforms to SS3654.
147
The rated output voltage is 24 V DC ± 1% for the main power source
(rectifier). Max. ripple 240 mVp-p. The rated output voltage for the second
power source (backup battery) is 20-27 V DC.
NOTE!
The voltage will,
however, decrease to approx. 15 V when the battery will be switched off in
order not to damage the battery.